Class 8839 58M Enclosed AC Drives

Specifications

1.04 WARRANTY

a.An 18-month parts warranty shall be provided on materials and workmanship from the date of invoice from an authorized distributor.

1.05 QUALITY ASSURANCE

a.The manufacturer of the AC Drive shall be a certified ISO 9001 facility.

b.The AC Drive and all associated optional equipment shall be UL LISTED according to UL508C Power Conversion Equipment. A UL label shall be attached inside each enclosure as verification.

c.The AC Drive shall be designed constructed and tested in accordance with NEMA, NEC, VDE, IEC standards.

d.Every power converter shall be tested with an actual ac induction motor, 100% load and temperature cycled within an environmental chamber at 104 °F. Documentation shall be furnished to verify successful completion at the request of the engineer.

e.All Drive door mounted pilot devices shall be tested to verify successful operation. Documentation shall be furnished upon written request of the engineer.

f.The AC Drive shall undergo QA test procedures and be submitted to a hi-pot test with all enclosed devices mounted and wired, prior to shipment.

PART 2 PRODUCT

2.01 MANUFACTURERS

a.The AC Drive shall be provided by Square D/ Groupe Schneider, Class 8839 58M Enclosed, Class 8839 Type CPDM “PowerGard™” or prior approved equal. Substitutions must be submitted in writing three (3) weeks prior to original bid date with supporting documentation demonstrating that the alternative manufacturer meets all aspects of the specifications herein.

b.Alternate control techniques other than pulse width modulated (PWM) are not acceptable.

2.02 GENERAL DESCRIPTION

Note to Specifier: For AC Drives rated up to

100 hp, the most practical harmonic mitigation technique can be line reactors, isolation transformers or harmonic suppressors dependent upon the type of power quality concerns. For AC Drives rated 125 hp and above, 18-Pulse offers a premium level of harmonic mitigation.

176

a.The AC Drive shall convert the input AC mains power to an adjustable frequency and voltage as defined below.

1.For AC Drives rated up to 100 hp, the AC Drive manufacturer shall use a 6-Pulse bridge rectifier design [with line reactors, isolation transformers for effective harmonic mitigation]. The diode rectifiers shall convert fixed voltage and frequency, AC line power to fixed DC voltage. The power section shall be insensitive to phase rotation of the AC line.

2.For AC Drives rated 125 hp and above, the AC Drive manufacturer shall supply an 18- Pulse topology using a multiple bridge rectifier design with integral reactor and phase shifting transformer. The 18-Pulse configuration shall result in a multiple pulse current waveform that approximates near sinusoidal input current waveform. The power section shall be insensitive to phase rotation of the AC line.

b.The output power section shall change fixed DC voltage to adjustable frequency AC voltage. This section shall use insulated gate bipolar transistors (IGBT) or intelligent power modules (IPM) as required by the current rating of the motor.

2.03 CONSTRUCTION

a.AC Drives rated 25 hp VT at 460 Vac and less shall be supplied in wall mounted enclosures unless compartmentalized, floor mounted enclosures are required for Barriered Bypass construction. (See Emergency Full Speed Requirements.) AC Drives rated 30 hp VT at 460 Vac and above shall be supplied in floor mounted enclosures.

b.Seismic ratings and certifications shall be provided for all floor mounted enclosures. The seismic ratings shall meet IBC 2000, NFPA 5000, ASCE 7-02, UBC zone 4, CDC zone 4 and the 1995 NBCC with exceptions for application in the British Columbia area and the New Madrid Hazard Zone. Verification of testing shall be in accordance with ICC AC156 Acceptance Criteria testing procedures. Enclosures shall exhibit a certification label on the inside enclosure door stating compliance to these requirements.

c.The AC Drive shall be mounted in a [Type 1, Type 12] enclosures with an external operated disconnect device. For AC Drives greater than 75 hp (CT) or 100 hp (VT), NEMA Type 12 or Type 1G ventilated enclosures with gaskets and filters are acceptable.

© 2000–2003 Schneider Electric All Rights Reserved

09/2003

Page 176
Image 176
Schneider Electric 58 TRX manual Part 2 Product