Altivar® 58 TRX AC Drives
Type F Drive Controllers
13
09/2003 © 2000–2003 Schneider Electric All Rights Reserved

ATV58 TRX TYPE F DRIVE CONTROLLERS

The ATV58 TRX family of adjustable-frequency AC drive controllers is used
to control three-phase asynchronous motors. ATV58 TRX Type F models
contain an ATV58 TRX Type H drive controller packaged in a compact Type
12 enclosure. They are for use in mechanical rooms, OEM equipm ent, and
factory floor applications requiring a local load break switch and input line
fusing. The following models are available:
1 to 7.5 hp (0.75 to 5.5 kW), 400/460 Vac, three-phase input
½ to 3 hp (0.37 to 2.2 kW), 200/240 Vac, single-phase i np ut
2 to 3 hp (1.5 to 2.2 kW), 200/240 Vac, three-phase input
Each ATV58 TRX Type F drive controller contains:
A Vario load break switch, input line fuses, and an ATV58 TRX drive
controller
Start Stop push buttons
A manual speed potentiometer mounted on the front of the enclosure
Space for one additional 16-mm operator
Four conduit openings that are closed with plugs
A transparent plastic door to allow viewing of status LEDs and a
separately supplied keypad
All ATV58 TRX communications and I/O options can be used in the Type F
drive controllers. The Type F drive controllers can be used on constant or
variable torque applications. The ratings are shown in the tables below.
200 Vac -10% / 240 Vac +10% at 50/60 Hz ±5%, Single-Phase Input with 3-Phase Output
Frame
SizeDrive Controller
Catalog Number
Motor PowerRated
Output Current Transient
Output Current
kW HP A A
1 ATV58EU09M2FZU 0.37 0.5 2.3 3.1
1 ATV58EU18M2FZU 0.75 1 4.1 5.6
2 ATV58EU29M2FZU 1.5 2 7.8 10.6
3 ATV58EU41M2FZU2.2 3 11 15
200 Vac -10% / 240 Vac +10% at 50/60 Hz ±5%, 3-Phase Input with 3-Phase Output
Frame
SizeDrive Controller
Catalog Number
Motor PowerRated
Output Current Transient
Output Current
kW HP A A
2 ATV58EU29M2FZU 1.5 2 7.8 10.6
3 ATV58EU41M2FZU 2.2 3 11 15
400 Vac -10% / 460 Vac +10% at 50/60 Hz ±5%, 3-Phase Input with 3-Phase Output
Frame
SizeDrive Controller
Catalog Number
Motor PowerRated
Output Current Transient
Output Current
kW HP A A
2 ATV58EU18N4FZU 0.75 1 2.3 3.1
2 ATV58EU29N4FZU 1.5 2 4.1 5.6
2 ATV58EU41N4FZU 2.2 3 5.8 7.9
3 ATV58EU54N4FZU 3 – 7.8 10.6
3 ATV58EU72N4FZU 4 5 10.5 14.3
3 ATV58EU90N4FZU 5.5 7.5 13 17.7
For dimensions, see page 122; for wiring diagrams, see pages 111 and 112.
Power indicated is for a switching frequency between 0.5 and 4 kHz, and at steady state. For switching
frequency between 8 and 16 kHz, use the next largest size drive controller . (For example, for 2 hp, order drive
controller ATV58EU41M2FZU.) If the duty cycle (that is, the drive controller run time) does not excee d 60% (36
second maximum for a 60 second cycle), this is not necessary.
For 60 seconds.
A line reactor (3% minimum) must be used with this drive controller.
ATV5 8 TRX Type F Product Family
ATV58NEMAb_w no back.tif