Class 8839 58M Enclosed AC Drives
Dimensions and Weights for Mounting
164 09/2003
© 2000–2003 Schneider Electric All Rights Reserved
Class 8839 58M Enclosed Drives: 25–75 hp CT Controllers and 30–100 hp VT Controllers @ 460
V and 15–40 hp CT Controllers and 15–50 hp VT Controllers @ 208/230 V
A
B
Ø1.50
(38.1)
Ø0.625
(15.875)
Lifting Holes
20.38
(517.7)
5.90
(149.9)
1.00
(25.4)
D
E
F
G
H
C
Conduit Entry - Top View
Conduit Entry - Bottom View
16.00
(406.4)
14.00
(355.6)
3.00
(76.2)
N
OTE:Remove plenum fan filter, front grill,
a
nd retaining bracket assembly to access
t
he mounting hole locations.
N
OTE:Provide at least 36 in. of mounting
c
learance in front of the drive controller and
a
t least 24 in. of mounting clearance at the
t
op of the drive controller. Floor-mounted
u
nits may be mounted side by side without
c
learance.
N
OTE:Remove the top or bottom conduit
p
lates as necessary to facilitate the
a
ppropriate conduit entry. Ensure that the
p
lates are replaced before working on the
d
rive controller.
hp Weight Enclosure Dimensions
Enclosure Size
460 V 208/230 V A B C D E F G H
CT VT CT VT lb kg in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm
25–40 30–50 15–20 15–25 378 171 83.38 2117.9 93.8 7 2384.3 84 2133.6 16.75 425.5 14.50 368.3 20 508 8.0 203.2 18 457.2 E
50–75 60–100 25–40 30–50 562 254 83.38 2117.9 93.87 2384.3 84 2133.6 23 584 19.00 482.6 25 635 8.0 203.2 23 584.2 F