Class 8998 Motor Control Centers
Space Requirements
Constant Torque 208/240 Vac Altivar 58 TRX AC Drives
|
|
| NEMA Type 1 and 1A |
|
|
|
| (Gasketed) | NEMA Type 12 |
|
|
|
|
|
Motor Rated Horsepower | Maximum Continuous |
|
| |
200 / 230 Vac | Output Current (A) | Space (Height) | Space (Height) | |
|
|
|
|
|
1 to 3 hp | 11 |
| 12” | 24” |
|
|
|
|
|
5 hp | 18 |
| 15” | 24” |
|
|
|
|
|
7.5 to 10 hp | 31 |
| 24” | 36” |
|
|
|
|
|
15 to 20 hp | 60 |
| 45” | 45” |
|
|
|
|
|
25 to 40 hp | 116 |
| 72” (20” wide) | 72” (20” wide) |
|
|
|
|
|
Variable Torque, Low Noise 480 Vac Altivar 58 TRX AC Drives
|
|
| NEMA Type 1 and 1A |
|
|
|
| (Gasketed) | NEMA Type 12 |
|
|
|
|
|
Motor Rated Horsepower | Maximum Continuous |
|
| |
460 Vac | Output Current (A) | Space (Height) | Space (Height) | |
|
|
|
|
|
0.5 to 3 hp | 5.8 |
| 12” | 24” |
|
|
|
|
|
5 to 7.5 hp | 13 |
| 15” | 24” |
|
|
|
|
|
10 to 15 hp | 24 |
| 24” | 36” |
|
|
|
|
|
20 hp | 33 |
| 27” | 36” |
|
|
|
|
|
25 to 40 hp | 52 |
| 45” | 45” |
|
|
|
|
|
50 to 75 hp | 96 |
| 72” (20” wide) | 72” (20” wide) |
|
|
|
|
|
Variable Torque, Low Noise 208/240 Vac Altivar 58 TRX AC Drives
|
|
| NEMA Type 1 and 1A |
|
|
|
| (Gasketed) | NEMA Type 12 |
|
|
|
|
|
Motor Rated Horsepower | Maximum Continuous |
|
| |
200 / 230 Vac | Output Current (A) | Space (Height) | Space (Height) | |
|
|
|
|
|
1 to 3 hp | 11 |
| 12” | 24” |
|
|
|
|
|
5 hp | 18 |
| 15” | 24” |
|
|
|
|
|
7.5 to 10 hp | 31 |
| 24” | 36” |
|
|
|
|
|
15 to 20 hp | 60 |
| 45” | 45” |
|
|
|
|
|
25 to 40 hp | 116 |
| 72” (20” wide) | 72” (20” wide) |
|
|
|
|
|
216
©