External RFI Input FiltersNOTE:Line reactors and filters are intended for separate mounting and wiring by the user. Ratings are based on NEC (NFPA 70) 430-150 current ratings. If the driv e has a higher FLA r ating, use the “A” rat ing to select the appropriate filter.
Supply Voltage ATV58 Models
Maximum Length of
Shielded Cable[1] Nominal
Current (In)
of the Filter Weight Catalog
Number
EN 55011
Class A EN 55022
Class B
Single-Phase
200 to 240 Vac
50/60 Hz
ATV58•U09M2, ATV58•U18M2 50 m/164 ft 20 m/65 ft 10 A 1.7 kg/3.7 lb VW3A58401
ATV58•U29M2, ATV58•U41M2 50 m/164 ft 20 m/65 ft 25 A 3.6 kg/7.9 lb VW3A58402
ATV58•U72M2 50 m/164 ft 20 m/65 ft 25 A 5.0 kg/11.0 lb VW3A58403
ATV58•U90M2, ATV58•D12M2 50 m/164 ft 20 m/65 ft 40 A 10.0 kg/22.0 lb VW3A58404
3-Phase
200 to 240 Vac
50/60 Hz
ATV58•U29M2, ATV58•U41M2 50 m/164 ft 20 m/65 ft 25 A 3.6 kg/7.9 lb VW3A58402
ATV58•U54M2, ATV58•U72M2 50 m/164 ft 20 m/65 ft 25 A 5.0 kg/11.0 lb VW3A58403
ATV58•U90M2, ATV58•D12M2 50 m/164 ft 20 m/65 ft 45 A 10.0 kg/22.0 lb VW3A58404
3-Phase
208 to 240 Vac
50/60 Hz
ATV58HD16M2X, ATV58HD23M2X n/a n/a 80 A 13.0 kg/28.6 lb VW3A58407
ATV58HD28M2X, ATV58HD33M2X,
ATV58HD46M2X n/a n/a 160 A 20.0 kg/44.0 lb VW3A58408
3-Phase
400 to 460 Vac
50/60 Hz
ATV58•U18N4, ATV58•U29N4,
ATV58•U41N4 50 m/164 ft 20 m/65 ft 25 A 3.6 kg/7.9 lb VW3A58402
ATV58•U54N4, ATV58•U72N4,
ATV58•U90N4 50 m/164 ft 20 m/65 ft 25 A 5.0 kg/11.0 lb VW3A58403
ATV58•D12N4, ATV58•D16N4 50 m/164 ft 20 m/65 ft 45 A 10.0 kg/22.0 lb VW3A58404
ATV58•D23N4 50 m/164 ft 20 m/65 ft 45 A 13.0 kg/28.6 lb VW3A58405
ATV58HD28N4 200 m/656 ft 100 m/328 ft 50 A 13.0 kg/28.6 lb VW3A58406
ATV58HD33N4, ATV58HD46N4 200 m/656 ft 100 m/328 ft 80 A 13.0 kg/28.6 lb VW3A58407
ATV58HD54N4, ATV58HD64N4,
ATV58HD79N4 200 m/656 ft 100 m/328 ft 160 A 20.0 kg/44.0 lb VW3A58408
[1]The filter selection tables give the maximum length for the shielded cables which connect the motors to the drive controllers for a switching frequency
of 0.5 to 12 kHz. These limits are given for information only as they depend on the interference capacity of the motors and the cables used. For motors
connected in parallel, the total of the lengths must be taken into account.
Line Reactors—480 V Rated Three Phase
460 V Drive Rating Open Style
Part Number Enclosed
Part Number
Approx.
Wt.
(lbs.)
Enclosure
Dimensions
HxWxD
(in.)
HP kW
1 . . . RL00202 RL00212 11 8x8x6
2–3 . . . RL00403 RL00413 12 8x8x6
5 . . . RL00803 RL00813 18 15x13x13
7.5 . . . RL01203 RL01213 25 15x13x13
10 . . . RL01803 RL01813 49 15x13x13
15 . . . RL02503 RL02513 49 15x13x13
20–25 . . . RL03503 RL03513 61 15x13x13
30 . . . RL04503 RL04513 70 15x13x13
40 . . . RL05503 RL05513 72 15x13x13
50–60 . . . RL08003 RL08013 86 15x13x13
75 . . . RL10003 RL10013 105 15x13x13
100 . . . RL13003 RL13013 105 15x13x13
125 . . . RL16003 RL16013 105 15x13x13
150 . . . RL20003 RL20013 131 15x13x13
200 . . . RL25003 RL25013 185 24x17x17
250 . . . RL32003 RL32013 235 24x17x17
300 . . . RL40003 RL40013 245 24x17x17
350–400 . . . RL50003 RL50013 335 24x17x17
450–500 . . . RL60003 RL60013 335 24x17x17
Line Reactors