Standard Features
STANDARD FEATURES
The Econoflex controller includes:
•Circuit breaker disconnect with lockout capability.
•Insulated Gate Bipolar Transistor (IGBT) power converter with PWM output waveform.
•
•Form C AFC fault contact, rated 2 A at 120 Vac, wired to customer terminal block.
•Form C AFC run contact, rated 2 A at 120 Vac, wired to customer terminal block.
•Fire/Freezestat interlock location provided to customer terminal block.
•Factory enclosed line reactor (25 to 100 HP at 460 Vac, 15 to 50 HP at 208/230 Vac).
•Top and bottom conduit knockouts for Type 1 and Type 12K.
•Industrial rated control operators.
•UL 508C listed with NEMA ICS 7.1 compliance.
•Instruction bulletin
When Bypass is selected the Econoflex controller also includes:
•Isolation and Bypass Contactors, mechanically and electrically interlocked.
•
•
•Class 20 overload protection.
Power Circuit Descriptions
•Power Circuit W operates the motor from the power converter.
•Power Circuit Y operates the motor from the power converter or from full voltage line power, bypass. The isolation and bypass contactors are mechanically and electrically interlocked. The two contactor isolation/bypass configurations sequence the contactors to provide the isolation of the motor when it is not running.
Test-Normal Selector Switch Description
The
•
•
•
Fire/Freezestat Interlock Description
User terminals are supplied for accepting a user supplied fire/freezestat interlock (normally closed). When the user supplied contact is opened the drive output isolation contactor and bypass contactor open and the motor stops.