Table 3: Recommended Fuses: 400/460 V Three-Phase Drive Controllers
F1-F2-F3 F1-F2-F3
Motor Drive Controller
CT, VTLN Line Power Fuses Drive Controller
VTLN Line Power Fuses
hp kW ATV58H••••• Class J [1] ATV58H••••• Class J [1]
10.75 U18N4 5
21.5 U29N4 10
32.2 U41N4 12
—3 U54N4 15
5 4 U72N4 20 U54N4X 20
7.5 5.5 U90N4 25 U72N4X 25
10 7.5 D12N4 40 U90N4X 40
15 11 D16N4 50 D12N4X 50
20 15 D23N4 70 D16N4X 70
25 18.5 D23N4X 70
hp kW CTLN
ATV58H••••• F1-F2-F3
Class J [2] CT, VTLN
ATV58H••••• F1-F2-F3
Class J [2] VT
ATV58H••••• F1-F2-F3
Class J [2]
20 11 D28N4 70
25 18.5 D33N4 80 D28N4 70 D28N4 70
30 22 D46N4 100 D33N4 80 D28N4 90
40 30 D54N4 125 D46N4 100 D33N4 110
50 37 D64N4 150 D54N4 125 D46N4 150
60 45 D79N4 200 D64N4 150 D54N4 175
75 55 D79N4 175 D64N4 200
100 75 D79N4 200
hp kW VT
ATV58H••••• F1-F2-F3 [3]
125 90 C10N4X FWH-300A
150 110 C13N4X FWH-400A
200 132 C15N4X FWH-500A
250 160 C19N4X FWH-600A
300 200 C23N4X FWH-700A
350 220 C25N4X FWH-800A
400 250 C28N4X FWH-900A
450 280 C31N4X FWH-900A
500 315 C33N4X FWH-1000A
[1] Fast-acting or time
delay Class J fuses are
acceptable. Class T
fuses are acceptable.
Class CC fuses may be
used if recommended
fuse rating is 30A or
lower.
[2] Fast-acting Class J
fuses. Class T fuses are
acceptable.
[3] Use the Bussmann
part numbers provided
or equivalent.
CT Constant Torque
CTLN Constant Torque Low
Noise
VTLN Variable Torque Low
Noise
VT Variable Torque