Altivar® 58 TRX AC Drives

Wiring Recommendations

Wiring Diagram for ATV58 TRX Type F Controllers (Three Phase)

L1 L2 L3

(1) Line Reactor

(2)(4)

 

L1

L2

L3

R1A

R1C

R1B

K13

K14

AO1 COM

AI1

+10

AI2

 

 

 

 

 

Fault

 

 

 

Manual

 

 

 

 

 

 

 

 

 

 

 

Speed

 

 

 

 

 

 

 

 

 

 

Potentiometer

F1

 

F2

F3

 

 

 

 

 

 

 

 

 

U

V

W

 

 

 

 

PA

 

PB

 

 

 

T1

T2

T3

 

 

 

 

 

 

 

 

 

 

(3)

COM

+24

LI1

LI2

LI3

LI4

(6)

STOP

START

 

 

 

 

 

 

 

 

Start-Stop Push Buttons with Seal-in Relay

3 Phase Type F.eps

M

Brake

(5)

3φ

Resistor

 

Notes

1.Line inductor, if required.

2.Fault relay contacts for remote signalling of the drive controller state. Contact state is shown with the controller de-energized or faulted.

3.User-installed wiring for using LI2, LI3, and LI4 with internal +24 V power supply. When using a +24 V external supply, connect the 0 V to the COM terminal. Do not use the +24 terminal on the control board but connect logic inputs to external +24 V.

4.K13 and K14 are open terminals available for customer use.

5.See page 34 for the available braking resistor kits.

6.Manual speed potentiometer and start-stop push buttons are factory-installed in the enclosure cover. There is enough space in the cover to install one more 16-mm operator.