Class 8839 58M Enclosed AC Drives
Factory Engineered Modifications
The standard enclosure dimensions of the Class 8839 58M Enclosed drives may not apply to orders containing
CONTROL OPTIONS
Form modifications in the E200 series cover control circuit engineered features for the Class 8839 58M Enclosed drive controller.
Mod E200
Menu-based message display center
Large full text screen display and setup of drive parameters. Provides meter display functions, I/O map, and fault message display
Note: The message display center replaces the standard keypad display.
Rules: Requires selection of 24 V power supply option Z10.
Mod | |
|
|
E201 | Analog percent speed meter scaled 0 to 120% base speed |
|
|
E202 | Analog percent current scaled 0 to 100% of rated output current |
|
|
E203 | Digital ammeter (amperes) scaled 0 to 2 times rated output amperes |
|
|
E204 | Digital speed meter (frequency) scaled 0 to 72 Hz output frequency |
|
|
E205 | Digital percent speed meter scaled 0 to 120% base speed |
|
|
E206 | Digital percent current scaled 0 to 100% of rated output current |
|
|
Rules: Limited to one meter selection unless Analog input option card (H09) is selected. If H09 is selected, one additional meter can be selected.
Mod E211
Door-mounted Modbus/PDA port
Provides one
Mod E212
Auxiliary drive run contacts
Provides three additional Form 'C' contacts rated 5 A @ 120 Vac wired to terminal blocks for customer use. Note: One Form 'C' contact for drive run is supplied as standard.
Rules: Available only if one additional N.O. Drive Run Contact standard option K10 is selected.
Mod E213
Auxiliary bypass run contacts
Provides three Form 'C' contacts rated 5 A @ 120 Vac wired to terminal blocks for customer use. Note: One N.O. contact for bypass run is supplied as standard when bypass is provided.
Rules: Available only if one additional N.O. Aux. Bypass Run Contact standard option M10 is selected.
Mod E214
Auxiliary drive fail contacts
Provides three Form 'C' contacts rated 5 A @ 120 Vac wired to terminal blocks for customer use. Note: One Form 'C' contact for drive fault indication is supplied as standard.
Rules: Available only if one additional N.O. Drive Fault Contact standard option L10 is selected.
Mod E215
Auxiliary auto mode contacts
Provides three Form 'C' contacts rated 5 A @ 120 Vac wired to terminal blocks for customer use.
Note: One N.O. contact for auto mode indication is supplied as standard when auto mode operation is provided.
Rules: Available only if one N.O. Auto Mode Contact standard option O10 is selected.
Mod E216
Adjustable restart delay timer
Provides an adjustable On Time Delay Relay for power up restart function, mounted and wired for AFC mode (hand or auto) mode and/or in the bypass mode (hand/auto).
Rules: Available on all configurations.
Mod E217
Motor space heater
Provides control circuit contacts, 120 V,
Rules: Available on all configurations.