wire.eps-2

 

24 V

LI1

LIx

ATV58 Control Terminals

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LI1 = Forward LIx = Reverse

Two Wire Control

ATV58 control terminals

-wire.eps

24 V

LI1

LI2

LIx

 

 

 

 

3

LI1 = Stop

LI2 = Forward

LIx = Reverse

 

Three Wire Control

Motor Frequency

PlusMinusSpd.eps

 

0

 

1

Stop

0

1

Forward

0

1

Reverse

0

Three Wire Control Timing Diagram

Frequency

 

 

AnalogInp.eps

HSP

 

 

 

 

 

LSP

 

 

 

0

 

 

AI 2

X

Y

20

(mA)

Analog Input 2 Scaling

09/2003

Altivar® 58 TRX AC Drives

Drive Control Parameters

DRIVE CONTROL PARAMETERS

Drive control parameters can be viewed and modified only when the access locking switch on the keypad display is in the total unlock position (see page 24). They can be modified only when the motor is stopped.

Two-Wire Control

The drive controller is factory-configured for two-wire control. The two-wire control function controls operation direction using maintained contacts. Depending on whether one or two directions of operation are required by the application, one or two logic inputs must be assigned to this function. An example of wiring for two-wire control is shown to the left. Three operating modes are possible:

Detection of the state of logic inputs.

Detection of a change in the state of logic inputs.

Detection of the state of logic inputs with Forward operation having priority over Reverse operation.

Three-Wire Control

The three-wire control function controls operation and stopping direction using momentary contacts. Depending on whether one or two directions of operation are required by the application, two or three logic inputs must be assigned to this function. An example of wiring for three-wire control is shown to the left. Three-wire control is appropriate for all types of applications with one or two operating directions.

Reverse Inhibit

This function disables reverse operation. It disables the REV key on the keypad display and also prohibits reverse operation commanded by the PI Regulator or Speed Reference Summation functions. Applications such as those involving pumps, fans, or other applications where reverse operation may cause mechanical damage may require reverse to be disabled.

Analog Input Configuration

This parameter allows Analog Input 2 (AI2) on the drive controller to be redefined to accept a range of signals. The input can be configured for 0 to 20 mA, 4 to 20 mA, or the minimum value (X) and maximum value (Y) can be user assigned by programming X and Y (with 0.1 mA resolution). Reverse- acting operation can also be configured. For example, 20 to 4 mA, where 20 mA equals low speed and 4mA equals high speed.

Keypad Command

When this parameter is set to Yes, the drive controller can be controlled by the keypad. The factory default is No. Enabling this parameter allows operation of the drive controller with the keypad RUN, STOP/RESET, and FWD/REV keys. In this mode of operation, the speed reference is entered in hertz or in customer defined units by using the keypad up or down arrow keys. Also, a logic input configured for Freewheel Stop, Fast Stop, or Stop by DC Injection will remain active at the control terminal strip.

Stop Priority

This parameter allows the keypad STOP key to remain active even if the drive is being commanded via the terminal strip or a serial connection. The factory default is Yes. If set to No, the keypad STOP key will not be active and the drive controller will not stop when it is pressed.

49

© 2000–2003 Schneider Electric All Rights Reserved

Page 49
Image 49
Schneider Electric 58 TRX manual Drive Control Parameters