Class 8839 Econoflex™ AC Drives
Sample Specifications
F.The combination enclosure shall include a 120 Vac smoke purge relay option [if required]. A user- supplied 120 Vac signal shall be sequenced in accordance with local fire protection codes and will switch the AC drive to 60 Hz operation for maximum fan motor speed. If drive bypass is supplied, the smoke purge relay will isolate the AC Drive and run the fan motor full speed on bypass.
G.The combination enclosure shall include terminal point connection for fire /freeze stat interlock, to prevent drive [or bypass] operation.
2.12 Drive Isolation & Bypass Contactors
A.The AC Drive shall include mechanically and electrically interlocked isolation and bypass contactors complete with Class 20 thermal overload relay, circuit breaker disconnect, control circuit transformer, AFC/OFF/BYPASS switch and TEST/NORMAL selector switch.
B.The operator shall have full control of the bypass starter by operation of the AFC/OFF/BYPASS selector switch.
C.In the AUTOMATIC mode of operation the bypass contactors shall be sequenced by the
D.The isolation contactor for the bypass shall be sequenced to provide motor isolation during a drive ready state of operation.
E.A TEST/NORMAL selector switch shall provide test operation of the power converter while operating the motor in bypass.
2.13 Harmonic Mitigation
A.The electrical distribution system has been designed to meet
PART 3: EXECUTION
The Enclosed AC Drive shall be Econoflex by Square D Company, Class 8839.
3.01 Inspection
A.Verify that the location is ready to receive work and the dimensions are as indicated.
3.02 Protection
A.Before and during the installation, the AC Drive equipment shall be protected from site contaminants.
3.03 Installation
A.Installation shall be in compliance with manufacturer's instructions, drawings and recommendations.
B.The AC Drive manufacturer shall provide a factory certified technical representative to inspect the
contractor's installation, test and
maximum total of [ | ] days. The | |
3.04 Training |
|
|
A. An | ] training days shall be provided by a representative of the AC |
Drive manufacturer to plant and/or maintenance personnel.
3.05 Documentation
A.The AC Drive manufacturer shall supply a comprehensive