Altivar® 58 TRX AC Drives
Communication Parameters
Monitoring Registers (Continued)
Word | Code | Units | Description | Possible Values or Range |
|
|
|
|
|
W489 | USPL | 0.01 | Lower byte of machine speed | Value read |
or 16#5FE8/28 |
|
|
|
|
|
|
|
|
|
W490 | USPH | 0.01 | Upper byte of machine speed | Value read |
or 16#5FE8/29 |
|
|
|
|
|
|
|
|
|
W491 | OPR | 1% | Output power estimated by the | Value read |
or 16#5FE8/2A |
|
| drive controller | 100% corresponds to nominal motor power |
|
|
|
|
|
W492 | AO1R | 0.002 mA | Image of analog output AO1. | Write authorized if AO1 = No (not assigned): |
or 16#5FE8/2B |
|
|
| 0 to 10000 (0 to 20 mA) |
|
|
|
| Read only if assigned: Value read |
|
|
|
|
|
W493 | UOP | 0.1 V | Voltage applied to the motor. | Value read |
or 16#5FE8/2C |
|
| Exists only on Type FVC models. |
|
|
|
|
|
|
W494 | APH | 1 kWh | Drive power meter (kWh) | Value read. |
or 16#5FE8/2D |
| or |
| If bit 15 = 0, units are kWh as given by bits 0 to 14. |
|
| 1 MWh |
| If bit 15 = 1, units are MWh as given by bits 0 to 14. |
|
|
|
|
|
W495 | RTH | 1 hr | Total motor run time | Value read |
or 16#5FE8/2E |
|
|
|
|
|
|
|
|
|
Special DRIVECOM Registers
Word | Code | Units | Parameter Name and Description | Possible Values or Range |
|
|
|
|
|
W600 | ERRD | — | ErrorCode | 16#0 = NOF: No fault |
or 16#603F |
|
| Fault code | 16#1000 = CRF: |
|
|
| Read/Write | or = OLF: Motor overload (calculation or PTC probes) |
|
|
|
| or = SOF: Overspeed |
|
|
|
| 16#2310 = OCF: Overcurrent (prolonged LIC) |
|
|
|
| 16#2320 = SCF: Motor |
|
|
|
| 16#3110 = OSF: Line supply overvoltage |
|
|
|
| 16#3120 = USF: Line supply undervoltage (> 200 ms) |
|
|
|
| 16#3130 = PHF: Line supply phase loss (> 1s) |
|
|
|
| 16#3310 = OBF: DC bus overvoltage |
|
|
|
| or = OPF: Motor phase loss |
|
|
|
| 16#4210 = OHF: Drive overheating (heatsink) |
|
|
|
| 16#4310 = OTF: Motor overheating (PTC probes) |
|
|
|
| 16#5520 = EEF: EEPROM memory fault |
|
|
|
| 16#6100 = INF: Internal fault |
|
|
|
| 16#6300 = CFF: Configuration incorrect (on initialization) |
|
|
|
| or = CFI: Configuration invalid (if writing a configuration) |
|
|
|
| 16#7300 = ANF: Ramp not followed |
|
|
|
| or = LFF: Loss of |
|
|
|
| or = TSF: Thermal sensor fault |
|
|
|
| 16#7310 = SPF: Speed feedback missing or miswired |
|
|
|
| 16#7510 = SLF: Serial link |
|
|
|
| 16#7520 = ILF: Fast serial link |
|
|
|
| or = CNF: Fast serial link communication network fault |
|
|
|
| 16#9000 = EPF: External fault |
|
|
|
|
|
W601 | CMDD | — | Controlword |
|
or 16#6040 |
|
| Command |
|
|
|
| Read/Write |
|
|
|
|
|
|
W602 | ETAD | — | Statusword |
|
or 16#6041 |
|
| Status |
|
|
|
| Write prohibited |
|
|
|
|
|
|
W603 | LFRD | 1 rpm [1] | SpeedSetP | |
or 16#6042 |
|
| Speed reference in rpm (reference not peak |
|
|
|
| limited) |
|
|
|
| Read/Write |
|
|
|
|
|
|
W604 | FRHD | 1 rpm | SpeedRef |
|
or 16#6043 |
|
| Ramp output (signed) in rpm |
|
|
|
| Write prohibited |
|
|
|
|
|
|
W605 | RFRD | 1 rpm [1] | SpeedActV |
|
or 16#6044 |
|
| Motor speed in rpm |
|
|
|
| Write prohibited |
|
|
|
|
|
|
W606 | SMIL | 1 rpm | SpdMinMax | 0 to HSP |
or 16#6046/1 |
|
| Minimum speed in 32 bits |
|
|
|
| Equivalent to LSP (W251), but in rpm |
|
|
|
| Read/Write |
|
|
|
|
|
|
W607 | SMIH |
| Reserved | 0 |
|
|
|
|
|
W608 | SMAL | 1 rpm | SpdMinMax | LSP to TFR |
or 16#6046/2 |
|
| Maximum speed in 32 bits |
|
|
|
| Equivalent to HSP (W250), but in rpm |
|
|
|
| Read/Write |
|
|
|
|
|
|
W609 | SMAH | — | Reserved | 0 |
|
|
|
|
|
[1] For ATV58 Type FVC, if CMI Bit 9 = 0, units are in rpm; if CMI Bit 9 = 1, units are in 0.015 Hz.
90
© |
| 09/2003 |
| ||
|
|
|