Altivar® 58 TRX AC Drives
Wiring Recommendations
Ratings for Input Line Currents, Type N 400 to 460 Vac
| Dissipated Power at Rated | Short Circuit Rating | Input Line Current | ||
Drive Controller Catalog Number | Load (Total) | ||||
|
|
| |||
|
|
|
| ||
| W | A RMS sym. | A | A | |
|
|
|
|
| |
ATV58NU18N4• | 57 | 5,000 | 3.4 | 2.6 | |
|
|
|
|
| |
ATV58NU29N4• | 97 | 5,000 | 6 | 4.5 | |
|
|
|
|
| |
ATV58NU41N4• | 120 | 5,000 | 7.8 | 6 | |
|
|
|
|
| |
ATV58NU54N4• | 170 | 5,000 | 10.2 | 7.8 | |
|
|
|
|
| |
ATV58NU72N4• | 210 | 5,000 | 13 | 10.1 | |
|
|
|
|
| |
ATV58NU90N4• | 295 | 5,000 | 17 | 13.2 | |
|
|
|
|
| |
ATV58ND12N4• | 360 | 22,000 | 26.5 | 21 | |
|
|
|
|
|
Output Wiring Precautions
The drive controller is sensitive to the amount of capacitance (either
Follow the guidelines below when selecting output cable:
•Cable type: the cable selected must have a low capacitance
•Cable length: the longer the cable, the greater the capacitance. Cable lengths greater than 100 ft (30.5 m) may affect controller and/or motor performance. For installations where cable length capacitances may be a problem, installing a reactor between the drive controller and the motor will increase inductance and decrease capacitance between cable conductors.
•Proximity to other output cables: because of high frequency switching and increased capacitance, the drive controller may fault under some conditions.
•Do not use lightning arrestors and/or power factor correction capacitors on the output of the drive controller.
NOTE: Provide at least 20 in. (500 mm) of cable at the drive controller output (U, V, W).
Grounding
For safe, dependable operation, ground the drive controller according to National Electrical Code and all local codes. To ground the drive controller:
•Connect a copper wire from the ground terminal on the drive controller (see the terminal locations on page 18) to the power system ground conductor. Wire size is determined by the drive controller size and by national and local codes.
•Verify that resistance to ground is one ohm or less. Improper grounding causes intermittent and unreliable operation.
.
YES
Drive Controller
Drive Controller
Drive Controller
|
| NO | ||
|
|
|
|
|
Drive Controller |
| Drive Controller | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Drive Controller |
| Drive Controller | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Drive | Controller |
Ground multiple drive controllers as shown in the figure to the left. Use one grounding conductor per device. Do not loop ground conductors or install them in series
106
© |
| 09/2003 |
| ||
|
|
|