| Altivar® 58 TRX AC Drives | |
| Type H Specifications | |
Electrical Specifications (Continued) | ||
|
|
|
Analog output AO1 | ||
| Factory setting: | |
| Maximum load impedance: 500 Ω | |
| Resolution: 0.04 mA (9 bits) | |
| Linearity: +/- 0.2 mA | |
| Accuracy: +/- 0.2 mA | |
| The analog output is updated every 2 mS, maximum. | |
|
|
|
Logic inputs LI | 4 assignable logic inputs with impedance 3.5 kW, compatible with PLC level | |
| 1, standard IEC | |
| Maximum length of shielded cable: 100 m (328 ft). | |
| Power supply + 24 Vdc (minimum 11 Vdc, maximum 30 Vdc). | |
| State 0 if < 5 Vdc, state 1 if ≥ 11 Vdc. | |
| Sampling time: 2 ms maximum. | |
| Other inputs: see option cards. | |
|
|
|
Logic outputs LO | 2 relay logic outputs for R1 (fault relay) and R2 (assignable). | |
| Form C, 1 N.O., 1 N.C. contact protected against overvoltages (relay R1). | |
| 1 N.O. contact protected against overvoltages (relay R2). | |
| Minimum switching capacity: 10 mA for 24 Vdc. | |
| Maximum switching capacity: on a resistive load (cos ϕ = 1): 5 A for 250 Vac | |
| or 30 Vdc; on an inductive load (cos ϕ = 0.4 and L/R = 7 ms): 1.5 A for 250 | |
| Vac or 30 Vdc. | |
| Other outputs: see option cards | |
|
|
|
Communication | RS 485 multidrop serial link with simplified Modbus protocol as part of the | |
| standard product. | |
| Transmission speed: 19200 bps, no parity | |
| Use: connecting a terminal (option), microprocessor card, a PC (option), or | |
| connecting one or more PLCs. | |
|
|
|
Codes and standards | UL Listed per UL 508C as incorporating electronic overload protection: | |
| UL File E164874 CCN NMMS | |
| ATV58HU09M2 to D46M2 | |
| ATV58HU18N4 to D79N4 | |
| ATV58HC10N4X to C33N4X | |
| CSA Certified to CSA C22.2 No. 14. | |
| CSA File LR96921 Class 3211 06 | |
| ATV58HU09M2 to D46M2 | |
| ATV58HU18N4 to D79N4 | |
| CE Marked | |
| Conforms to applicable NEMA ICS, NFPA, IEC, and ISO 9001 standards. | |
|
|
|
117