COM

AI 3A

AI 3B

+ 10

- 10

AO

LI 5

LI 6

+ 24

LO

AnalogIOTerms.eps

Terminals for the I/O Extension Card with Analog Inputs

Altivar® 58 TRX AC Drives

I/O Extension Cards

I/O Extension Card with Analog Inputs (VW3A58201U)

This model includes two 24 Vdc logic inputs, one 24 Vdc open collector logic output, one 0 to 20 mA X-Y configurable analog output, and one bipolar ±10 Vac analog input. The analog input may be used for speed correction with a tachogenerator, for feedback of the PI function, for processing of PTC motor protection probes, or for summing the frequency reference.

The figure to the left shows the location of the terminals for this I/O card. The following tables describe the terminal functions and characteristics. See page 50 for a summary of configurable I/O functions.

Functions and Characteristics of Terminals

Terminal

Function

Characteristics

 

 

 

COM

Common for analog inputs and outputs

0 V

 

 

 

AI3A

Differential analog input

± 10 V, impedance = 30 k

 

 

AI3B

Differential analog input

 

 

 

 

+10

Supply for analog inputs

+ 10 V, Is = 10 mA maximum

 

 

 

-10

Supply for analog inputs

- 10 V, Is = 10 mA maximum

 

 

 

AO

Analog output

0 - 20 mA, (x - y configurable)

Load impedance = 500 maximum

 

 

 

 

 

LI5

 

2 logic inputs

 

Logic inputs

Impedance = 3.5 k

LI6

 

Supplied by +24 V

 

 

 

+24

Supply for logic inputs

+24 V, Is = 200 mA maximum

LO

Logic output

Open collector output

 

 

 

LO+

Supply for logic output

+24 V supply, Is = 20 mA maximum

 

 

 

The 200 mA is the sum of the current supplied by the +24 on the control board and the +24 on the I/O extension card.

Specifications

 

Protected against short circuits and overloads

Available internal supplies

1 output +10 V ± 1%, Is = 10 mA maximum

1 output -10 V ±1%, Is = 10 mA maximum

 

1 output +24 V (20 V min., 30 V max.), Is = 200 mA maximum

 

2 reassignable logic inputs. Impedance = 3.5 k. Compatible with level 1 PLCs

 

according to IEC 65A-68. Maximum shielded cable length: 330 ft (100 m).

Logic Inputs LI

Supply: +24 Vac (11 V min., 30 V max.)

 

State 0 if < 5 V, state 1 if > 11 V.

 

The logic inputs are sampled every 5 ms, maximum.

 

 

 

1 reassignable open collector logic output, compatible with level 1 PLCs according to

 

IEC 65A-68.

Logic Output LO

Supply: +24 V (12 V min., 30 V max.),

 

maximum current = 20 mA with internal source or 200 mA with external source.

 

The logic output is updated every 5 ms, maximum.

 

 

 

1 reassignable 0 - 20 mA analog output, (x - y configurable).

 

Maximum load impedance = 500 .

Analog Output AO

Resolution: 0.04 mA (9 bits)

Linearity: ± 0.1 mA

 

 

Accuracy: ± 0.2 mA

 

The analog output is updated every 5 ms, maximum.

 

 

 

1 reassignable 0 ± 10 V bipolar differential input.

 

Impedance = 30 k. Adjustable gain.

 

Maximum allowable voltage: ± 30 V

 

Freq. reference resolution: 0.1 Hz for 100 Hz (0.1% of max. freq.), 10 bits plus sign.

Analog Input AI

Accuracy: ± 0.5%

Linearity: ± 0.2% of the maximum output frequency

 

 

The analog input is sampled every 5 ms, maximum.

 

Maximum length of shielded cable: 66 ft (20 m)

 

If configured for thermal sensors, use 750 maximum at 20 °C (68 °F)

 

(three 250 sensors in series).

 

 

The 200 mA is the sum of the current supplied by the +24 on the control board and the +24 on the I/O extension card.

27