Altivar® 58 TRX AC Drives
Installation Recommendations
Mounting in a General-Purpose Metal Enclosure
To ensure sufficient air circulation when mounting an ATV58 TRX drive in a
• Provide ventilation inlets and outlets in the enclosure (see the figure below).
| VentEnc.eps |
free air flow | with fan and filter |
| mounted on enclosure |
•If the enclosure does not provide sufficient free air flow, install an enclosure ventilation fan with IP54/NEMA 12 filters to exhaust heat outside of the enclosure (see the figure above). The enclosure fan should have a greater fan flow rate than the drive controller fan flow rate listed in the table below.
ATV58 TRX Model | Fan Flow Rate |
|
|
|
|
ATV58HU09M2, ATV58U18M2 |
| |
|
|
|
ATV58HU29M2, ATV58U18N4, ATV58U29N4, ATV58U41N4, ATV58U54N4 | 36 m3/hour | 21 CFM |
ATV58HU41M2 | 47 m3/hour | 27.5 CFM |
ATV58HU54M2, ATV58U72M2, ATV58U54N4, ATV58U72N4, ATV58U90N4 | 72 m3/hour | 42 CFM |
ATV58HU90M2, ATV58D12M2, ATV58D12N4, ATV58D16N4, ATV58D23N4 | 72 m3/hour | 42 CFM |
ATV58HD16M2, ATV58D23M2, ATV58D28N4, ATV58D33N4, ATV58D46N4 | 161 m3/hour | 94 CFM |
ATV58HD28M2, ATV58D33M2, ATV58D46M2, ATV58D54N4, ATV58D64N4, ATV58D79N4 | 343 m3/hour | 200 CFM |
ATV58HC10N4X | 600 m3/hour | 350 CFM |
ATV58HC13N4X, C15N4X, C19N4X | 900 m3/hour | 525 CFM |
ATV58HC23N4X, C25N4X, C28N4X, C31N4X, C33N4X | 900 m3/hour | 525 CFM |
•If there is a possibility of condensation, keep the control supply switched on during periods when the motor is not running, or install thermostatically controlled strip heaters.
Mounting in a Type 12 or IP54 Metal Enclosure
Certain conditions may require Type 12 or IP54 protection, such as dust, corrosive gas, high humidity with the risk of condensation and dripping water. When mounting in a Type 12 or IP54 enclosure, follow the installation recommendations given on page 97.
If the enclosure is