Altivar® 58 TRX AC Drives
Communication Parameters
91
09/2003 © 2000–2003 Schneider Electric All Rights Reserved
W610
or 16#6048/1 SPAL 1 rpm SpdAcc
Acceleration ramp determined by a speed
variation in rpm via words W610 and W611
(32 bits) plus a time variation in seconds
given by word W612 (16 bits)
Read/Write
1 to 65535
W611 SPAH — Reserved 0
W612
or 16#6048/2 SPAT 1 s SpdAcc
Acceleration ramp determined by a speed
variation in rpm via words W610 and W611
(32 bits) plus a time variation in seconds
given by word W612 (16 bits)
Read/Write
0 to 65535
W613
or 16#6049/1 SPDL 1 rpm SpdDec
Deceleration ramp determined by a speed
variation in rpm via words W613 and W614
(32 bits) plus a time variation in seconds
given by word W615 (16 bits)
Read/Write
1 to 65535
W614 SPDH — Reserved 0
W615
or 16#6049/2 SPDT 1 s SpdDec
Deceleration ramp determined by a speed
variation in rpm via words W613 and W614
(32 bits) plus a time variation in seconds
given by word W615 (16 bits)
Read/Write
0 to 65535
Special DRIVECOM Registers (Continued)

Word Code Units Parameter Name and Description Possible Values or Range