Altivar® 58 TRX AC Drives

 

 

 

 

Communication Parameters

Special DRIVECOM Registers (Continued)

 

 

 

 

 

 

Word

Code

Units

Parameter Name and Description

Possible Values or Range

 

 

 

 

 

W610

SPAL

1 rpm

SpdAcc

1 to 65535

or 16#6048/1

 

 

Acceleration ramp determined by a speed

 

 

 

 

variation in rpm via words W610 and W611

 

 

 

 

(32 bits) plus a time variation in seconds

 

 

 

 

given by word W612 (16 bits)

 

 

 

 

Read/Write

 

 

 

 

 

 

W611

SPAH

Reserved

0

 

 

 

 

 

W612

SPAT

1 s

SpdAcc

0 to 65535

or 16#6048/2

 

 

Acceleration ramp determined by a speed

 

 

 

 

variation in rpm via words W610 and W611

 

 

 

 

(32 bits) plus a time variation in seconds

 

 

 

 

given by word W612 (16 bits)

 

 

 

 

Read/Write

 

 

 

 

 

 

W613

SPDL

1 rpm

SpdDec

1 to 65535

or 16#6049/1

 

 

Deceleration ramp determined by a speed

 

 

 

 

variation in rpm via words W613 and W614

 

 

 

 

(32 bits) plus a time variation in seconds

 

 

 

 

given by word W615 (16 bits)

 

 

 

 

Read/Write

 

 

 

 

 

 

W614

SPDH

Reserved

0

 

 

 

 

 

W615

SPDT

1 s

SpdDec

0 to 65535

or 16#6049/2

 

 

Deceleration ramp determined by a speed

 

 

 

 

variation in rpm via words W613 and W614

 

 

 

 

(32 bits) plus a time variation in seconds

 

 

 

 

given by word W615 (16 bits)

 

 

 

 

Read/Write

 

 

 

 

 

 

91

09/2003

 

© 2000–2003 Schneider Electric All Rights Reserved

 

 

 

 

Page 91
Image 91
Schneider Electric 58 TRX manual Spal, Spah, Spat, Spdl, Spdh, Spdt