NOTE: The input conductor ampacity rating should not be less than the ampacity rating selected based on the rated controller output current.

Altivar® 58 TRX AC Drives

Wiring Recommendations

Ratings for Input Line Currents, Types E and F 200 Vac -10% / 240 Vac +10% Three-Phase Input with Three-Phase Output

 

 

Motor Power at 4 kHz

Rated

 

 

Input Line Current

 

 

 

 

 

 

 

 

Drive Controller

Switching Frequency

Output

 

5000 AIC

with Additional 3%

Current (In)

 

 

 

 

Line Impedance

Catalog Number

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

kW

HP

A

200 V

 

240 V

200 V

240 V

 

 

A

 

A

A

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ATV58EU29M2ZU

1.5

2

7.8

9.7

 

8.3

6.6

5.9

 

 

 

 

 

 

 

 

 

ATV58EU41M2ZU

2.2

3

11

13.4

 

11.4

9.5

8.5

 

 

 

 

 

 

 

 

 

 

Ratings for Input Line Currents, Types E and F 400 Vac -15% / 460 Vac +20% Three-Phase Input with Three-Phase Output

 

 

 

Rated

Input Line Current

 

 

 

Motor Power at 4 kHz

Output

 

 

 

 

 

 

 

with Additional 3%

Drive Controller

Switching Frequency

Current

5000 AIC

 

 

Line Impedance

Catalog Number

 

 

(In)

 

 

 

 

 

 

 

 

 

400 V

460 V

A

400 V

460 V

400 V

460 V

 

kW

HP

A

A

A

A

 

 

 

 

 

 

 

 

 

 

ATV58EU18N4ZU

0.75

1

2.3

3.4

2.6

1.9

1.6

 

 

 

 

 

 

 

 

ATV58EU29N4ZU

1.5

2

4.1

6

4.5

3.3

3

 

 

 

 

 

 

 

 

ATV58EU41N4ZU

2.2

3

5.8

7.8

6

4.8

4.2

 

 

 

 

 

 

 

 

ATV58EU54N4ZU

3

7.8

10.2

7.8

6.3

5.6

 

 

 

 

 

 

 

 

ATV58EU72N4ZU

4

5

10.5

13

10.1

8.6

7.2

 

 

 

 

 

 

 

 

ATV58EU90N4ZU

5.5

7.5

13

17

13.2

11.8

10.1

 

 

 

 

 

 

 

 

Ratings for Input Line Currents, Type N 208 to 230 Vac

Single-Phase Input with Three-Phase Output / Three-Phase Input with Three-Phase Output

208 to 230 Vac, Single-Phase Input with 3-Phase Output

 

Dissipated Power at Rated

Short Circuit Rating

Input Line Current

Drive Controller Catalog Number

Load (Total)

 

 

 

 

 

 

 

 

W

A RMS sym.

A

A

 

 

 

 

 

ATV58NU09M2•

42

2,000

5.6

4.7

 

 

 

 

 

ATV58NU18M2•

64

2,000

9.8

8.3

 

 

 

 

 

ATV58NU29M2•

107

5,000

18.5

15.6

 

 

 

 

 

ATV58NU41M2•

160

5,000

25.6

21.6

When these drive controllers are used with a single-phase input, a line reactor (3% minimum) must be used.

 

 

208 to 230 Vac, 3-Phase Input with 3-Phase Output

 

 

 

 

 

 

 

 

 

Dissipated Power at Rated

Short Circuit Rating

Input Line Current

Drive Controller Catalog Number

Load (Total)

 

 

 

 

 

 

 

 

W

A RMS sym.

A

A

 

 

 

 

 

ATV58NU29M2•

107

5,000

9.7

8.3

 

 

 

 

 

ATV58NU41M2•

160

5,000

13.4

11.4

 

 

 

 

 

ATV58NU54M2•

190

5,000

17.2

15

 

 

 

 

 

ATV58NU72M2•

240

5,000

22.4

19.5

 

 

 

 

 

105

09/2003

 

© 2000–2003 Schneider Electric All Rights Reserved

 

 

 

 

Page 105
Image 105