Class 8839 58M Enclosed AC Drives
Factory Engineered Modifications
Mod E218
Signal loss follower alarm relay
Provides one Form 'C' contact rated 5 A @ 120 Vac wired to terminal blocks for customer use. Intended for
Note: Requires use of logic output LO1.
Rules: Available on all configurations.
Mod E219
Inhibit/shutdown sequence (timed operation)
Provides a relay circuit operating in the fail safe mode where a remote initiating contact opens the relay, deenergizes, and after a specified time shuts the drive controller down in the AFC mode (hand or auto) and/or in the bypass mode (hand or auto).
Rules: Available on all configurations.
Mod E220
Check valve sequence (motorized type)
Provides relay circuitry sequenced from a check valve limit switch. A valve closed position limit switch will energize relays that will initiate a remote valve operating solenoid limited to 50 VA and give a run permissive to the drive controller in the AFC mode (hand or auto) and/or in the bypass mode (hand or auto). A valve closed position limit switch will
Rules: Available on all configurations.
Mod E221
Seal water solenoid - with pressure switch feedback
Provides a relay, which will energize a remote seal water solenoid limited to 50 VA during drive controller operation. Additionally, the remote initiating contact will open the relay, deenergize, and after a specified time shut the drive controller down in the AFC mode (hand or auto) and/or in the bypass mode (hand or auto).
Rules: Available on all configurations.
Mod E222
Moisture detection relay circuit (without relay)
Provides 24 V or 120 V control power to a
Note: Customer supplies relay. Details concerning type must also be provided at time of order entry in the 'Engineering Notes' field within Q2C.
Rules: Available on all configurations.
Mod E223
Moisture detection relay circuit (with relay)
Provides 24 V or 120 V control power to a
Note: Details concerning type must be provided at time of order entry in the 'Engineering Notes' field within Q2C.
Rules: Available on all configurations.
Mod E224
Substitute Type K operators
Provides Class 9001 Type K 30 mm heavy duty multifunction operators in place of standard Telemecanique 22 mm pilot devices.
Rules: Available on all configurations.
Mod E225
Spare control relays
Provides unwired control relays mounted for customer use.
Rules: Available on all configurations.
Mod E226
Substitute pilot light lens color(s)
Provides the flexibility to configure lens cap colors to contract equipment designations.Note: specify lens cap colors desired at time of order entry in 'Engineering Notes' field within Q2C.
Rules: Available on all configurations.
Mod E227
Blown fuse indicators on control fuses
Provides blown circuit fuse indicators on control circuit fuses in lieu of standard fuses.
Rules: Available on all configurations.
Mod E228
Motor over temperature logic input
Provides dedicated terminals using an external motor over temperature input (N.C. contact) factory wired and programmed.
Rules: Available on all configurations.