Class 8839 58M Enclosed AC Drives

Standard Modifications

MISCELLANEOUS OPTIONS

Mod A10

Line Reactor (5%)

Line reactors (5% effective impedance) are provided inside the drive enclosure. Line reactors are wired in the power converter circuit and do not affect operation of full speed bypass if provided.

Mod B10

Line Contactor

Provides a line contactor option for bypass power circuits. The line contactor is opened when the drive controller is not commanded to run or is in the bypass mode of operation. This option is not available with Barriered Bypass (option 910)

Mod C10

3–15 psi Transducer

Allows the drive controller to follow a user supplied 3–15 psi input.

Mod D10

Omit Keypad

The keypad is not supplied. The user must buy a keypad as a separate device to program the drive controller.

Mod E10

Smoke Purge

Provides a smoke purge operating mode controlled by a user-supplied 120 Vac signal wired to terminal block TB1. Smoke purge operation is full speed bypass (when provided) or high speed in the drive controller. This operation is designed to run the motor from any operator control setting except emergency stop or open safety interlocks

Mod G10

CSA / cUL Certification

Provides Canadian cUL or CSA certification when required by local code requirements.

Mod H10

Seismic Certification (Floor Mounted Enclosures)

Provides a floor-mounted enclosure certified to seismic rating AC156 harmonized with NFPA 5000 and IBC 2000 standards.

Mod J10

0–10 V Auto Speed Reference

Provides a controller interface for 0–10 Vdc user-supplied auto speed reference signal to the AI2 input using a 0–10V/4–20mA converter (part number 31158-297-50). Source impedance: Z=40kW.

Mod K10

1 Additional N.O. Auxiliary Drive Run Contact

Provides 1 additional N.O. contact for drive run indication wired to TB1.

Mod L10

1 Additional N.C. Auxiliary Drive Fault Contact

Provides 1 additional N.C. contact for drive fault indication wired to TB1.

Mod M10

1 N.O. Auxiliary Bypass Run Contact

Provides 1 additional N.O. contact for bypass run indication wired to TB1.

Mod O10

1 N.O. Auxiliary Auto Mode Contact

Provides 1 additional N.O. contact for auto mode indication wired to TB1.

Mod P10

Drive Fault Reset Pushbutton

Provides a factory-installed door-mounted push button to reset the controller fault when Hand-Off-Auto in not used.

Mod Q10

Push-To-Test Pilot Lights

Provides push-to-test function on all pilot lights except Power On.

Mod R10

Auto Transfer to Bypass

Provides an automatic transfer (time adjustable 0.1–10 s) to bypass in the event that the drive controller faults. A selector switch is provided inside the enclosure to enable or disable this function. Longer transfer time requirements are available by replaceable plug-in adjustable timer.

Mod S10

Motor Elapsed Time Meter

Provides an elapsed time meter to record the motor run time. Runs whenever the motor is running.

Mod T10

Emergency Stop Mushroom Head Pushbutton

Provides a door-mounted maintained off emergency stop red mushroom pushbutton with turn-to-reset feature.

09/2003

153

© 2000–2003 Schneider Electric All Rights Reserved

Page 153
Image 153
Schneider Electric 58 TRX manual Miscellaneous Options