Class 8839 58M Enclosed AC Drives

Motor Protecting Output Filters

Low pass filters can be used on the output of the Class 8839 58M Enclosed AC Drive to decease the stress of resonant frequencies on the attached motor. While low pass filters are not necessary for most installations, they do provide substantial benefits in installations involving long motor leads, such as:

460 V or higher rated AC drives

1–25 hp rated units, if cable lead lengths are in excess of 75 feet

30–400 hp rated units, if cable lead lengths are in excess of 300 feet

Use of a non–inverter duty rated motor(s)

Existing general purpose motors subject to retrofit to an AC drive

The motor protecting output filters combine inductance, capacitance, and resistance to form a low pass filter. This filter will lower the dV/dt levels to prevent exciting the natural resonant wire frequency of the motor cables. Motors compliant to NEMA MG–1 Part 31 guidelines do not require the use of motor protecting output filters.

HP Rating

Output Filter Part No.

Separately Mounted

@ 460 V

(Separate Mounting)

Engineered Option

 

 

 

1–2

KLCUL4A1

E402

 

 

 

3

KLCUL6A1

E402

 

 

 

5

KLCUL8A1

E402

 

 

 

7.5

KLCUL12A1

E402

 

 

 

10

KLCUL16A1

E402

 

 

 

15

KLCUL25A1

E402

 

 

 

20–25

KLCUL35A1

E402

 

 

 

30

KLCUL45A1

E402

 

 

 

40

KLCUL55A1

E402

 

 

 

50-60

KLCUL80A2

E402

 

 

 

75

KLCUL110A2

E402

 

 

 

100

KLCUL130A2

E402

 

 

 

125

KLCUL160A2

E402

 

 

 

150

KLCUL200A3

E402

 

 

 

200

KLCUL250A3

E402

 

 

 

250

KLCUL300A3

E402

 

 

 

300

KLCUL360A3

E402

 

 

 

350

KLCUL420A3

E402

 

 

 

400

KLCUL480A3

E402

 

 

 

450–500

KLCUL600A3

E402

 

 

 

Motor Protecting Output Filters:

1.Output filters are manufactured by Trans-Coil, Inc.

2.Output filters are designed for cable lead lengths ranging from 50 to 1000 feet.

3.Output filters include 1.5% nominal reactance at 480 V.

4.Output filters are enclosed in Type 1 general purpose enclosures.

5.Output filters are intended for separate mounting and wiring by user.

09/2003

161

© 2000–2003 Schneider Electric All Rights Reserved

Page 161
Image 161