Class 8839 Econoflex™ AC Drives

Ratings

INPUT CURRENT RATINGS (CONTINUED)

Input Line Currents for Selection of Branch Circuit Feeder for Class 8839 Econoflex 230 Vac

 

Motor Power

5 kAIC

22 kAIC

Factory-mounted Line Reactor

Drive Controller

Mod A09

 

230 Vac 60 Hz

(0.141 mH)

(0.032 mH)

 

 

 

Catalog Number

5 kAIC (0.141 mH)

22 kAIC (0.032 mH)

(HP)

(A)

(A)

 

(A)

(A)

 

 

 

 

 

 

 

 

 

 

58EC•3V_

1

4.9

5.6

3.3

3.5

 

 

 

 

 

 

58ED•3V_

2

8.6

9.7

5.6

5.9

 

 

 

 

 

 

58EE•3V_

3

11.8

13.4

8.1

8.5

 

 

 

 

 

 

58EF•3V_

5

19.5

22.1

14.1

14.7

 

 

 

 

 

 

58EG•3V_

7.5

26.4

30

19.9

20.6

 

 

 

 

 

 

58EH•3V_

10

35

38.2

27.5

28.6

 

 

 

 

 

 

58EJ•3V_

15

37.8

38

37.8

38

 

 

 

 

 

 

58EK•3V_

20

50.5

50.8

50.5

50.8

 

 

 

 

 

 

58EL•3V_

25

61.8

61.8

61.8

61.8

 

 

 

 

 

 

58EM•3V_

30

73.3

73.6

73.3

73.6

 

 

 

 

 

 

58EN•3V_

40

97.9

98.5

97.9

98.5

 

 

 

 

 

 

58EP•3V_

50

121.2

124

121.2

124

 

 

 

 

 

 

Input Line Currents for Selection of Branch Circuit Feeder for Class 8839 Econoflex 208 Vac

 

Motor Power

5 kAIC

22 kAIC

Factory-mounted Line Reactor

Drive Controller

Mod A09

 

208 Vac 60 Hz

(0.141 mH)

(0.032 mH)

 

Catalog Number

5 kAIC (0.141 mH)

22 kAIC (0.032 mH)

(HP)

(A)

(A)

 

 

(A)

(A)

 

 

 

 

 

 

 

 

 

 

58EC•2V_

1

5.3

6

3.7

3.8

 

 

 

 

 

 

58ED•2V_

2

9.4

10.6

6.5

6.6

 

 

 

 

 

 

58EE•2V_

3

13

14.5

9.2

9.5

 

 

 

 

 

 

58EF•2V_

5

21.4

24

16.2

17.1

 

 

 

 

 

 

58EG•2V_

7.5

29

34.7

22.9

23.3

 

 

 

 

 

 

58EH•2V_

10

38.3

44.4

31.7

32.3

 

 

 

 

 

 

58EJ•2V_

15

41.7

41.7

41.7

41.7

 

 

 

 

 

 

58EK•2V_

20

55.5

55.7

55.5

55.7

 

 

 

 

 

 

58EL•2V_

25

67

67.2

67

67.2

 

 

 

 

 

 

58EM•2V_

30

80.9

80.9

80.9

80.9

 

 

 

 

 

 

58EN•2V_

40

107.6

108.4

107.6

108.4

 

 

 

 

 

 

58EP•2V_

50

134.8

135.5

134.8

135.5

 

 

 

 

 

 

Select conductor based on the input line current.

The • may be A or G; A denotes a Type 12K enclosure; G denotes a Type 1 enclosure. The underscore (_) indicates that the catalog number continues. See page 186 for detailed description of catalog numbers.

Factory modification A09 is optional for 1 to 20 HP controllers and included in 25 to 100 HP controllers.

196

© 2000–2003 Schneider Electric All Rights Reserved

09/2003

Page 196
Image 196
Schneider Electric 58 TRX manual 196