Class 8839 Econoflex™ AC Drives
Ratings
196 09/2003
© 2000–2003 Schneider Electric All Rights Reserved
INPUT CURRENT RATINGS (CONTINUED)
Input Line Currents for Selection of Branch Circuit Feeder for Class 8839 Econoflex 230 Vac
Drive Controller
Catalog Number
Motor Power
230 Vac 60 Hz
(HP)
5 kAIC
(0.141 mH)
(A)
22 kAIC
(0.032 mH)
(A)
Factory-mounted Line Reactor
Mod A09
5 kAIC (0.141 mH)
(A) 22 kAIC (0.032 mH)
(A)
58EC•3V_ 1 4.9 5.6 3.3 3.5
58ED•3V_ 2 8.6 9.7 5.6 5.9
58EE•3V_ 3 11.8 13.4 8.1 8.5
58EF•3V_ 5 19.5 22.1 14.1 14.7
58EG•3V_ 7.5 26.4 30 19.9 20.6
58EH•3V_ 10 35 38.2 27.5 28.6
58EJ•3V_ 15 37.8 38 37.8 38
58EK•3V_ 20 50.5 50.8 50.5 50.8
58EL•3V_ 25 61.8 61.8 61.8 61.8
58EM•3V_ 30 73.3 73.6 73.3 73.6
58EN•3V_ 40 97.9 98.5 97.9 98.5
58EP•3V_ 50 121.2 124 121.2 124
Input Line Currents for Selection of Branch Circuit Feeder for Class 8839 Econoflex 208 Vac
Drive Controller
Catalog Number
Motor Power
208 Vac 60 Hz
(HP)
5 kAIC
(0.141 mH)
(A)
22 kAIC
(0.032 mH)
(A)
Factory-mounted Line Reactor
Mod A09
5 kAIC (0.141 mH)
(A) 22 kAIC (0.032 mH)
(A)
58EC•2V_ 1 5.3 6 3.7 3.8
58ED•2V_ 2 9.4 10.6 6.5 6.6
58EE•2V_ 3 13 14.5 9.2 9.5
58EF•2V_ 5 21.4 24 16.2 17.1
58EG•2V_ 7.5 29 34.7 22.9 23.3
58EH•2V_ 10 38.3 44.4 31.7 32.3
58EJ•2V_ 15 41.7 41.7 41.7 41.7
58EK•2V_ 20 55.5 55.7 55.5 55.7
58EL•2V_ 25 67 67.2 67 67.2
58EM•2V_ 30 80.9 80.9 80.9 80.9
58EN•2V_ 40 107.6 108.4 107.6 108.4
58EP•2V_ 50 134.8 135.5 134.8 135.5
Select conductor based on the input line current.
The • may be A or G; A denotes a Type 12K enclosure; G denotes a Type 1 enclosure. The underscore (_) indicates that the catalog number
continues. See page 186 for detailed description of catalog numbers.
Factory modification A09 is optional for 1 to 20 HP controllers and included in 25 to 100 HP controllers.