Class 8839 Econoflex™ AC Drives
Ratings
INPUT CURRENT RATINGS (CONTINUED)
Input Line Currents for Selection of Branch Circuit Feeder for Class 8839 Econoflex 230 Vac▲
| Motor Power | 5 kAIC | 22 kAIC |
| ||
Drive Controller | Mod A09 |
| ||||
230 Vac 60 Hz | (0.141 mH) | (0.032 mH) |
| |||
|
| |||||
Catalog Number▼ | 5 kAIC (0.141 mH) | 22 kAIC (0.032 mH) | ||||
(HP) | (A) | (A) | ||||
| (A) | (A) | ||||
|
|
|
| |||
|
|
|
|
|
| |
58EC•3V_ | 1 | 4.9 | 5.6 | 3.3 | 3.5 | |
|
|
|
|
|
| |
58ED•3V_ | 2 | 8.6 | 9.7 | 5.6 | 5.9 | |
|
|
|
|
|
| |
58EE•3V_ | 3 | 11.8 | 13.4 | 8.1 | 8.5 | |
|
|
|
|
|
| |
58EF•3V_ | 5 | 19.5 | 22.1 | 14.1 | 14.7 | |
|
|
|
|
|
| |
58EG•3V_ | 7.5 | 26.4 | 30 | 19.9 | 20.6 | |
|
|
|
|
|
| |
58EH•3V_ | 10 | 35 | 38.2 | 27.5 | 28.6 | |
|
|
|
|
|
| |
58EJ•3V_ | 15 | 37.8 | 38 | 37.8 | 38 | |
|
|
|
|
|
| |
58EK•3V_ | 20 | 50.5 | 50.8 | 50.5 | 50.8 | |
|
|
|
|
|
| |
58EL•3V_ | 25 | 61.8 | 61.8 | 61.8 | 61.8 | |
|
|
|
|
|
| |
58EM•3V_ | 30 | 73.3 | 73.6 | 73.3 | 73.6 | |
|
|
|
|
|
| |
58EN•3V_ | 40 | 97.9 | 98.5 | 97.9 | 98.5 | |
|
|
|
|
|
| |
58EP•3V_ | 50 | 121.2 | 124 | 121.2 | 124 | |
|
|
|
|
|
|
Input Line Currents for Selection of Branch Circuit Feeder for Class 8839 Econoflex 208 Vac▲
| Motor Power | 5 kAIC | 22 kAIC |
| ||
Drive Controller | Mod A09 |
| ||||
208 Vac 60 Hz | (0.141 mH) | (0.032 mH) |
| |||
Catalog Number▼ | 5 kAIC (0.141 mH) | 22 kAIC (0.032 mH) | ||||
(HP) | (A) | (A) | ||||
| ||||||
| (A) | (A) | ||||
|
|
|
| |||
|
|
|
|
|
| |
58EC•2V_ | 1 | 5.3 | 6 | 3.7 | 3.8 | |
|
|
|
|
|
| |
58ED•2V_ | 2 | 9.4 | 10.6 | 6.5 | 6.6 | |
|
|
|
|
|
| |
58EE•2V_ | 3 | 13 | 14.5 | 9.2 | 9.5 | |
|
|
|
|
|
| |
58EF•2V_ | 5 | 21.4 | 24 | 16.2 | 17.1 | |
|
|
|
|
|
| |
58EG•2V_ | 7.5 | 29 | 34.7 | 22.9 | 23.3 | |
|
|
|
|
|
| |
58EH•2V_ | 10 | 38.3 | 44.4 | 31.7 | 32.3 | |
|
|
|
|
|
| |
58EJ•2V_ | 15 | 41.7 | 41.7 | 41.7 | 41.7 | |
|
|
|
|
|
| |
58EK•2V_ | 20 | 55.5 | 55.7 | 55.5 | 55.7 | |
|
|
|
|
|
| |
58EL•2V_ | 25 | 67 | 67.2 | 67 | 67.2 | |
|
|
|
|
|
| |
58EM•2V_ | 30 | 80.9 | 80.9 | 80.9 | 80.9 | |
|
|
|
|
|
| |
58EN•2V_ | 40 | 107.6 | 108.4 | 107.6 | 108.4 | |
|
|
|
|
|
| |
58EP•2V_ | 50 | 134.8 | 135.5 | 134.8 | 135.5 | |
|
|
|
|
|
|
▲Select conductor based on the input line current.
▼The • may be A or G; A denotes a Type 12K enclosure; G denotes a Type 1 enclosure. The underscore (_) indicates that the catalog number continues. See page 186 for detailed description of catalog numbers.
■Factory modification A09 is optional for 1 to 20 HP controllers and included in 25 to 100 HP controllers.
196
©