Class 8839 Econoflex™ AC Drives
Ratings
CONTROLLER RATINGS
Class 8839 ATV58 Econoflex Drive Controller Ratings 460 Vac
Drive Controller | Motor Power▲ | Maximum Continuous | Max. Transient (60 s) | Power Converter |
Catalog Number◆ | 460 Vac 60 Hz (HP) | Output Current (A)■ | Output Current (A) | Part Number |
58EC•4V_ | 1 | 2.1 | 2.3 | FLEX58U18N4 |
|
|
|
|
|
58ED•4V_ | 2 | 3.4 | 3.7 | FLEX58U29N4 |
|
|
|
|
|
58EE•4V_ | 3 | 4.8 | 5.3 | FLEX58U41N4 |
|
|
|
|
|
58EF•4V_ | 5 | 7.6 | 8.4 | FLEX58U72N4 |
|
|
|
|
|
58EG•4V_ | 7.5 | 11 | 12.1 | FLEX58U90N4 |
|
|
|
|
|
58EH•4V_ | 10 | 14 | 15.4 | FLEX58D12N4 |
|
|
|
|
|
58EJ•4V_ | 15 | 21 | 23.1 | FLEX58D16N4 |
|
|
|
|
|
58EK•4V_ | 20 | 27 | 29.7 | FLEX58D23N4 |
|
|
|
|
|
58EL•4V_ | 25 | 34 | 37.4 | FLEX58D28N4 |
|
|
|
|
|
58EM•4V_ | 30 | 40 | 44 | FLEX58D28N4 |
|
|
|
|
|
58EN•4V_ | 40 | 52 | 57.2 | FLEX58D33N4 |
|
|
|
|
|
58EP•4V_ | 50 | 65 | 71.5 | FLEX58D46N4 |
|
|
|
|
|
58EQ•4V_ | 60 | 77 | 84.7 | FLEX58D54N4 |
|
|
|
|
|
58ER•4V_ | 75 | 96 | 105.6 | FLEX58D64N4 |
|
|
|
|
|
58ES•4V_ | 100 | 124 | 136.4 | FLEX58D79N4 |
|
|
|
|
|
Class 8839 ATV58 Econoflex Drive Controller Ratings 230 Vac |
| |||
|
|
|
|
|
Drive Controller | Motor Power▲ | Maximum Continuous | Max. Transient (60 s) | Power Converter |
Catalog Number◆ | 230 Vac 60 Hz (HP) | Output Current (A)■ | Output Current (A) | Part Number |
58EC•3V_ | 1 | 4.2 | 4.6 | FLEX58U29M2 |
|
|
|
|
|
58ED•3V_ | 2 | 6.8 | 7.5 | FLEX58U29M2 |
|
|
|
|
|
58EE•3V_ | 3 | 9.6 | 10.5 | FLEX58U41M2 |
|
|
|
|
|
58EF•3V_ | 5 | 15.2 | 16.7 | FLEX58U72M2 |
|
|
|
|
|
58EG•3V_ | 7.5 | 22 | 24.2 | FLEX58U90M2 |
|
|
|
|
|
58EH•3V_ | 10 | 28 | 30.8 | FLEX58D12M2 |
|
|
|
|
|
58EJ•3V_ | 15 | 42 | 46.2 | FLEX58D16M2 |
|
|
|
|
|
58EK•3V_ | 20 | 54 | 59.4 | FLEX58D16M2 |
|
|
|
|
|
58EL•3V_ | 25 | 68 | 74.8 | FLEX58D23M2 |
|
|
|
|
|
58EM•3V_ | 30 | 80 | 88 | FLEX58D28M2 |
|
|
|
|
|
58EN•3V_ | 40 | 104 | 114.4 | FLEX58D33M2 |
|
|
|
|
|
58EP•3V_ | 50 | 130 | 143 | FLEX58D46M2 |
|
|
|
|
|
◆The • may be A or G; A denotes a Type 12K enclosure; G denotes a Type 1 enclosure. The underscore (_) indicates that the catalog number
continues. See page 186 for detailed description of catalog numbers.
▲Power shown is for a carrier switching frequency of 8 kHz. For a switching frequency between 12 and 1 6kHz, select the next largest size drive controller. If the duty cycle does not exceed 60% (36 s maximum for a 60 s cycle), this is not necessary.
■Continuous output current based on NEC table
194
©
09/2003