Class 8998 Motor Control Centers
Sample Specifications
shall be connected directly to the main horizontal bus with appropriately size cable or riser bus.
f.All AC drive controller units shall be enclosed in a structure which contains a 12" (305 mm) high horizontal wireway at the top of each section, and a 6" (152 mm) high horizontal wireway at the bottom of each section. These wireways should be unobstructed the full length of the motor control center to allow room for power and control cable to connect between units in different sections.
g.A
h.All AC drive controller unit interior mounting panels shall be white for better visibility inside.
i.The motor control center structure shall include unit mounting shelves with hanger brackets to support AC drive controller units up to 50 hp variable torque during installation and removal. A twin handle camming lever shall be located at the top of AC drive controller units up to 50 hp variable torque to rack the unit in and out.
j.A cast metal handle operator shall be provided on each AC drive controller unit disconnect. With the AC drive controller unit connected to the motor control center bus and the AC drive controller unit door closed, the handle mechanism shall allow complete on/off control of the unit disconnect, with clear indication of the disconnect’s status. All circuit breaker operators shall include a separate tripped position to clearly indicate a circuit breaker trip condition. It shall be possible to reset a tripped circuit breaker without opening the control unit door.
1.A mechanical interlock shall prevent an operator from opening the AC drive controller unit door when the disconnect is in the on position. Another mechanical interlock shall prevent an operator from placing the disconnect in the on position while the AC drive controller unit door is open. It shall be possible for authorized personnel to defeat these interlocks.
2.A
k.Provisions shall be provided for locking all disconnects in the off position with up to three padlocks.
l.All
m.Handle mechanisms shall be located on the left side to encourage operators to stand to the left of the unit being switched.
n.Unit construction shall combine with the vertical wireway isolation barrier to provide a fully compartmentalized design.
o.All AC drive controller units shall be provided with unit control terminal blocks for use in terminating field wiring. Terminal blocks shall be
2.04 Thermal Management
a.The AC drive controller unit shall incorporate a
b.The AC drive controller unit cooling system shall be sized to cool the drive regardless of mounting location within the motor control center. The AC drive controller unit shall not be restricted to a specific location in the motor control center.
09/2003