Configurable I/O Functions

Drive Address

This parameter is used to set the address when controlling the drive controller by a Modbus device via the RS-485 port. The baud rate is selectable as 9600 or 19,200 bits/sec.The range of addresses is 0 to 31. The factory setting is 0, indicating that the drive controller is not being controlled via the RS-485 port.

Reset Counters

This parameter can be used to reset the watt-hour meter or the run time meter back to zero.

CONFIGURABLE I/O FUNCTIONS

Configurable I/O Functions can be viewed and modified only when the access locking switch on the keypad display is in the total unlock position (see page 24). These parameters can be modified only when the motor is stopped.

Default I/O Configurations

Selecting a macro-configuration automatically assigns the inputs and outputs to functions suitable for the application. The table below shows the drive controller I/O assignment as a function of the macro- configuration selected.

Factory-Configured Functions for the Three Macro-Configurations

 

Material Handling[1]

General Use

Variable Torque

Basic I/O

 

 

 

 

 

 

 

Logic input LI1

Forward

Forward

Forward

 

 

 

 

Logic input LI2

Reverse

Reverse

Reverse

 

 

 

 

Logic input LI3

2 preset speeds

Jog operation

Auto-Manual [3]

Logic input LI4

4 preset speeds

Freewheel stop/Run permissive [2]

DC injection braking [3]

Analog input AI1

Reference summing

Reference summing

Speed reference 1 [3]

Analog input AI2

Reference summing

Reference summing

Speed reference 2 [3]

Analog output AO1

Motor frequency

Motor frequency

Motor frequency

 

 

 

 

Relay R1

Drive fault relay

Drive fault relay

Drive fault relay

 

 

 

 

Relay R2

Output contactor control

Motor thermal state attained

Frequency reference attained [3]

Analog or Digital I/O Extension Cards

 

 

 

 

 

 

Logic input LI5

8 preset speeds

Fault reset

Freewheel stop

 

 

 

 

Logic input LI6

Fault reset

Current limit

Ramp switching

 

 

 

 

Analog input AI3 (analog I/O card)

Summing speed reference

Summing speed reference

PI regulator

or

 

 

 

Speed regulation

Speed regulation

Speed regulation

Encoder Inputs (digital I/O card)

 

 

 

 

Logic output LO

Current threshold attained

Output contactor control

High speed attained

 

 

 

 

Analog output AO

Motor current

Motor current

Motor current

 

 

 

 

[1]Factory default setting for 100 hp products and below.

[2]If the Freewheel Stop/Run Permissive function is configured, the drive controller will not start the motor unless the logic input is connected to +24 V.

[3]For 125–500 hp controllers, the factory settings are:

LI3 = fault reset; LI4 = Not assigned; AI1 = Reference summing; AI2 = Reference summing; R2 = Drive running.

Assignable I/O Functions

The table below shows the possible I/O assignments for the ATV58 TRX Type H drive controller and the optional I/O Extension Cards. Only one I/O extension card or one communication card can be installed in the drive.

The following I/O are on the drive controller.

Logic Input 1 (LI1) is configured for Run Forward when the drive controller is set for two wire control and configured for STOP when the drive controller is set for three wire control.

Relay Output 1 (R1) is configured as a fault relay (1 N.O. contact and 1 N.C. contact) and cannot be re-assigned.

50