Altivar® 58 TRX AC Drives
Macro-Configuration Programming
MACRO-CONFIGURATION PROGRAMMING
ATV58 TRX drives have a
•Material handling (factory default setting)
•General use
•Variable torque
NOTE:
Selecting one of the
The
| Material Handling[1] | General Use | Variable Torque | |
Basic I/O |
|
|
| |
|
|
|
| |
Logic input LI1 | Forward | Forward | Forward | |
|
|
|
| |
Logic input LI2 | Reverse | Reverse | Reverse | |
|
|
|
| |
Logic input LI3 | 2 preset speeds | Jog operation | ||
Logic input LI4 | 4 preset speeds | Freewheel stop/Run permissive [2] | DC injection braking [3] | |
Analog input AI1 | Reference summing | Reference summing | Speed reference 1 [3] | |
Analog input AI2 | Reference summing | Reference summing | Speed reference 2 [3] | |
Analog output AO1 | Motor frequency | Motor frequency | Motor frequency | |
|
|
|
| |
Relay R1 | Drive fault relay | Drive fault relay | Drive fault relay | |
|
|
|
| |
Relay R2 | Output contactor control | Motor thermal state attained | Frequency reference attained [3] | |
Analog or Digital I/O Extension Cards |
|
| ||
|
|
|
| |
Logic input LI5 | 8 preset speeds | Fault reset | Freewheel stop | |
|
|
|
| |
Logic input LI6 | Fault reset | Current limit | Ramp switching | |
|
|
|
| |
Analog input AI3 (analog I/O card) | Summing speed reference | Summing speed reference | PI regulator | |
or |
|
|
| |
Speed regulation | Speed regulation | Speed regulation | ||
Encoder Inputs (digital I/O card) | ||||
|
|
|
| |
Logic output LO | Current threshold attained | Output contactor control | High speed attained | |
|
|
|
| |
Analog output AO | Motor current | Motor current | Motor current | |
|
|
|
|
[1]Factory default setting for 100 hp products and below.
[2]If the Freewheel Stop/Run Permissive function is configured, the drive controller will not start the motor unless the logic input is connected to +24 V.
[3]For
LI3 = fault reset; LI4 = Not assigned; AI1 = Reference summing; AI2 = Reference summing; R2 = Drive running.
DRIVE CONTROLLER IDENTIFICATION SCREEN:
INCREASING POWER RATING FOR VARIABLE TORQUE APPLICATIONS
This screen can always be displayed, and shows the power rating and voltage of the drive controller. It can also be used to increase the power rating for variable torque applications using 208/230 Vac drive controllers of at least 10 hp or 460 Vac drive controllers of 3 to 100 hp.