Altivar® 58 TRX AC Drives

Dynamic Braking Resistor Kits

Current/Time Characteristics for DB Resistor Assemblies

The figure below shows the allowable GV2 trip times as a function of current setting multiples with the dynamic braking resistor assembly located in a 40 °C (104 °F) ambient temperature environment. See page 35 for an example of how to calculate resistor size.

10000

DynBrkCurves.eps

 

1000

 

100

Cold State

 

10

 

Time(s)

 

1

 

Hot State

0.1

0.01

0.001

1

1.5

10

100

 

 

Multiples of current setting (lr)

 

The kits in the following table use the thermal protection of a GV2 manual starter and have a Type 1 rating per UL 50. The insulation system is suitable for use in a Pollution Degree 3 environment (refer to NEMA ICS-1 Annex A). The package is UL/CSA marked.

DB Kits Technical Specifications

Dynamic Braking Kit for:

Ohmic Value

Continuous Current Rating

Average Power

Catalog Number

(Rdb)

of Assembly(Ir)

(W)

ATV58•U09M2, ATV58•U18M2,

 

 

 

 

ATV58•U18N4, ATV58•U29N4,

120

1.0 A

120

VW3A66711

ATV58•U41N4, ATV58•U54N4,

 

 

 

 

ATV58•U72N4

 

 

 

 

 

 

 

 

 

ATV58•U29M2, ATV58•U41M2,

56

1.45 A

118

VW3A66712

ATV58•U90N4, ATV58•D12N4

 

 

 

 

 

 

 

 

 

ATV58•U54M2, ATV58•U72M2,

28

2.7 A

204

VW3A66713

ATV58•D16N4, ATV58•D23N4

 

 

 

 

 

 

 

 

 

ATV58•U90M2, ATV58•D12M2,

14

 

 

 

ATV58•D28N4, ATV58•D33N4,

3.8 A

202

VW3A66714

ATV58•D46N4

 

 

 

 

 

 

 

 

 

ATV58•D16M2, ATV58•D23M2,

10

10.0 A

1000

VW3A66715

ATV58•D54N4

 

 

 

 

 

 

 

 

 

ATV58•D28M2, ATV58•D33M2,

5

 

 

 

ATV58•D46M2, ATV58•D64N4,

14.0 A

980

VW3A66716

ATV58•D79N4

 

 

 

 

 

 

 

 

 

Current rating of resistor assembly is calculated based on setting of internal overload protective device in assembly, overload setting based on enclosure overtemperature protection, and resistor overload versus time characteristics. Resistors are rated for stopping six times rotor inertia of four- pole motor with drive at current limit. Motor inertias are based on NEMA MG-1 14.45.

Requires external braking transistor, VW3A58701.

37

09/2003

 

© 2000–2003 Schneider Electric All Rights Reserved

 

 

 

 