Maintenance and Testing
a.Display the user parameter list by pressing  .
.
b.Use the arrow keys to scroll through the parameters until the display shows “Battery capacity test: xxx.”
c.Switch the battery capacity test “OFF” by pressing  .
.
5.Wait until the display shows “Normal operation load power xx%” and a short alarm sounds.
6.Press  . The display will show “Battery capacity test: xxx.” (“xxx” = the estimated backup time in minutes)
. The display will show “Battery capacity test: xxx.” (“xxx” = the estimated backup time in minutes)
7.Press  to exit the user parameter list.
 to exit the user parameter list.
| 26 | User Guide APC BC300 Series 40kW 208/450/480V UPS | 