Maintenance and Testing

a.Display the user parameter list by pressing .

b.Use the arrow keys to scroll through the parameters until the display shows “Battery capacity test: xxx.”

c.Switch the battery capacity test “OFF” by pressing .

5.Wait until the display shows “Normal operation load power xx%” and a short alarm sounds.

6.Press . The display will show “Battery capacity test: xxx.” (“xxx” = the estimated backup time in minutes)

7.Press to exit the user parameter list.

990-1403

26

User Guide APC BC300 Series 40kW 208/450/480V UPS

Page 26
Image 26
APC BC300 manual Maintenance and Testing