
Alarms and Events
Table 5: Possible Alarms
| TSM 1 temp. | Inverter module 1 has shut down | Find the vents for the UPS fans | 
| shutdown | because the temperature on the | and check to see if the fans are | 
| 
 | operating. Do not try to open the | |
| 
 | shutdown level. If bypass is within | unit, and do not insert anything | 
| 
 | tolerance, the unit transfers to | into a fan vent. If the fans are not | 
| 
 | static bypass operation. If not, the | operating, call APC Global | 
| 
 | unit transfers to  | Service. | 
| 
 | and does not supply output voltage. | If the fans are operating, make | 
| 
 | 
 | sure the room temperature is | 
| 
 | 
 | below 80° F (27° C). If not, cool | 
| 
 | 
 | down the room. if the room was | 
| 
 | 
 | already below this temperature, | 
| 
 | 
 | call APC Global Service. | 
| 
 | 
 | 
 | 
| TSM 1 temp. | The temperature on the  | Find the vents for the UPS fans | 
| warning | for inverter module 1 has exceeded | and check to see if the fans are | 
| 
 | the warning setting. The unit’s | operating. Do not try to open the | 
| 
 | status does not change. However, if | unit, and do not insert anything | 
| 
 | the temperature continues to rise, | into a fan vent. If the fans are not | 
| 
 | the unit will sound a “TSM 1 temp. | operating, call APC Global | 
| 
 | shutdown” alarm. | Service. | 
| 
 | 
 | If the fans are operating, make | 
| 
 | 
 | sure the room temperature is | 
| 
 | 
 | below 80° F (27° C). If not, cool | 
| 
 | 
 | down the room. if the room was | 
| 
 | 
 | already below this temperature, | 
| 
 | 
 | call APC Global Service. | 
| 
 | 
 | 
 | 
| TSM 2 temp. | Inverter module 2 has shut down | Find the vents for the UPS fans | 
| shutdown | because the temperature on the | and check to see if the fans are | 
| 
 | operating. Do not try to open the | |
| 
 | shutdown level. If bypass is within | unit, and do not insert anything | 
| 
 | tolerance, the unit transfers to | into a fan vent. If the fans are not | 
| 
 | static bypass operation. If not, the | operating, call APC Global | 
| 
 | unit transfers to  | Service. If the fans are operating, | 
| 
 | not supply output voltage. | make sure the room temperature | 
| 
 | 
 | is below 80° F (27° C). If not, cool | 
| 
 | 
 | down the room. if the room was | 
| 
 | 
 | already below this temperature, | 
| 
 | 
 | call APC Global Service. | 
| 
 | 
 | 
 | 
| TSM 2 temp. | The temperature on the  | Find the vents for the UPS fans | 
| warning | for inverter module 2 is higher than | and check to see if the fans are | 
| 
 | the warning setting. The unit’s | operating. Do not try to open the | 
| 
 | status does not change. However, if | unit, and do not insert anything | 
| 
 | the temperature continues to rise, | into a fan vent. If the fans are not | 
| 
 | the unit will sound a “TSM 2 temp. | operating, call APC Global | 
| 
 | shutdown” alarm. | Service. If the fans are operating, | 
| 
 | 
 | make sure the room temperature | 
| 
 | 
 | is below 80° F (27 °C). If not, cool | 
| 
 | 
 | down the room. if the room was | 
| 
 | 
 | already below this temperature, | 
| 
 | 
 | call APC Global Service. | 
| 
 | 
 | 
 | 
| 
 | 
 | 
| User Guide APC BC300 Series 40kW 208/450/480V UPS | 21 | 
