Alarms and Events

Table 5: Possible Alarms

TSM 1 temp.

Inverter module 1 has shut down

Find the vents for the UPS fans

shutdown

because the temperature on the

and check to see if the fans are

 

heat-sink is higher than the

operating. Do not try to open the

 

shutdown level. If bypass is within

unit, and do not insert anything

 

tolerance, the unit transfers to

into a fan vent. If the fans are not

 

static bypass operation. If not, the

operating, call APC Global

 

unit transfers to stand-by mode

Service.

 

and does not supply output voltage.

If the fans are operating, make

 

 

sure the room temperature is

 

 

below 80° F (27° C). If not, cool

 

 

down the room. if the room was

 

 

already below this temperature,

 

 

call APC Global Service.

 

 

 

TSM 1 temp.

The temperature on the heat-sink

Find the vents for the UPS fans

warning

for inverter module 1 has exceeded

and check to see if the fans are

 

the warning setting. The unit’s

operating. Do not try to open the

 

status does not change. However, if

unit, and do not insert anything

 

the temperature continues to rise,

into a fan vent. If the fans are not

 

the unit will sound a “TSM 1 temp.

operating, call APC Global

 

shutdown” alarm.

Service.

 

 

If the fans are operating, make

 

 

sure the room temperature is

 

 

below 80° F (27° C). If not, cool

 

 

down the room. if the room was

 

 

already below this temperature,

 

 

call APC Global Service.

 

 

 

TSM 2 temp.

Inverter module 2 has shut down

Find the vents for the UPS fans

shutdown

because the temperature on the

and check to see if the fans are

 

heat-sink is higher than the

operating. Do not try to open the

 

shutdown level. If bypass is within

unit, and do not insert anything

 

tolerance, the unit transfers to

into a fan vent. If the fans are not

 

static bypass operation. If not, the

operating, call APC Global

 

unit transfers to stand-by and does

Service. If the fans are operating,

 

not supply output voltage.

make sure the room temperature

 

 

is below 80° F (27° C). If not, cool

 

 

down the room. if the room was

 

 

already below this temperature,

 

 

call APC Global Service.

 

 

 

TSM 2 temp.

The temperature on the heat-sink

Find the vents for the UPS fans

warning

for inverter module 2 is higher than

and check to see if the fans are

 

the warning setting. The unit’s

operating. Do not try to open the

 

status does not change. However, if

unit, and do not insert anything

 

the temperature continues to rise,

into a fan vent. If the fans are not

 

the unit will sound a “TSM 2 temp.

operating, call APC Global

 

shutdown” alarm.

Service. If the fans are operating,

 

 

make sure the room temperature

 

 

is below 80° F (27 °C). If not, cool

 

 

down the room. if the room was

 

 

already below this temperature,

 

 

call APC Global Service.

 

 

 

 

 

990-1403

User Guide APC BC300 Series 40kW 208/450/480V UPS

21

Page 21
Image 21
APC BC300 manual Alarms and Events