 | Alarms and Events | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | Table 5: Possible Alarms | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
| 
 | High output | The output voltage is higher than | If the alarm is still active, put the | 
 | 
| 
 | voltage (This | the alarm setting. The unit stays in | UPS into bypass by displaying | 
 | 
| 
 | alarm is usually | the normal operation mode. If the | the user parameters and | 
 | 
| 
 | only listed in the | alarm is not cleared, the unit will | changing “Bypass Operation” to | 
 | 
| 
 | events log) | transfer to static bypass operation | “ON.” (See the “Parameter | 
 | 
| 
 | 
 | if bypass is within tolerance. If | Settings” section in this User | 
 | 
| 
 | 
 | bypass is not within tolerance, the | Guide). Then, call APC Global | 
 | 
| 
 | 
 | unit will transfer to  | Service. | 
 | 
| 
 | 
 | will not supply output voltage. | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
| 
 | High temp. | The temperature in the main choke | Find the exhaust vents for the | 
 | 
| 
 | choke | is too high. If the problem is not | UPS fans and check to see if the | 
 | 
| 
 | 
 | corrected soon, the unit will | fans are operating. Do not try to | 
 | 
| 
 | 
 | transfer to battery operation. | open the unit, and do not insert | 
 | 
| 
 | 
 | 
 | anything into a fan vent. If the | 
 | 
| 
 | 
 | 
 | fans are not operating, call APC | 
 | 
| 
 | 
 | 
 | Global Service. | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
| 
 | High temp. | The temperature in the main | Find the exhaust vents for the | 
 | 
| 
 | transformer | transformer is too high. If the | UPS fans and check to see if the | 
 | 
| 
 | 
 | problem is not corrected soon, the | fans are operating. Do not try to | 
 | 
| 
 | 
 | unit will transfer to  | open the unit, and do not insert | 
 | 
| 
 | 
 | will not supply output voltage. | anything into a fan vent. If the | 
 | 
| 
 | 
 | 
 | fans are not operating, call APC | 
 | 
| 
 | 
 | 
 | Global Service. | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
| 
 | Inverter fuse | One or more of the fuses at the | Call APC Global Service. | 
 | 
| 
 | blown | output of the inverter are blown | 
 | 
 | 
| 
 | 
 | (F004, F005, F006). If bypass is | 
 | 
 | 
| 
 | 
 | within tolerance, the unit transfers | 
 | 
 | 
| 
 | 
 | to static bypass operation. If not, | 
 | 
 | 
| 
 | 
 | the unit transfers to  | 
 | 
 | 
| 
 | 
 | does not supply output voltage. | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
| 
 | Inverter voltage | The output voltage is too high or too | If the UPS is in  | 
 | 
| 
 | error | low. If the alarm was caused by | the UPS by pressing the green | 
 | 
| 
 | 
 | high output voltage, the unit | button inside the door. If the UPS | 
 | 
| 
 | 
 | transfers to static bypass operation | will not restart, a user may have | 
 | 
| 
 | 
 | if bypass is within tolerance. If | started an emergency power off | 
 | 
| 
 | 
 | bypass is not within tolerance, the | (EPO) shutdown. Find out if the | 
 | 
| 
 | 
 | unit transfers to  | EPO shut down the UPS; if it did, | 
 | 
| 
 | 
 | not supply output voltage. If the | find out why and make sure the | 
 | 
| 
 | 
 | alarm was caused by low output | emergency situation has passed. | 
 | 
| 
 | 
 | voltage, the unit transfers to static | Then, reset the EPO and restart | 
 | 
| 
 | 
 | bypass operation if bypass is within | the unit by pressing the green | 
 | 
| 
 | 
 | tolerance. If bypass is not within | button inside the door. If the unit | 
 | 
| 
 | 
 | tolerance, the unit transfers to | will still not restart, call APC | 
 | 
| 
 | 
 | battery for five seconds and then | Global Service. | 
 | 
| 
 | 
 | transfers to  | 
 | 
 | 
| 
 | 
 | supplying output voltage. | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
| 16 | User Guide APC BC300 Series 40kW 208/450/480V UPS | 