| Alarms and Events |
|
|
|
|
|
|
|
|
|
|
|
|
| Table 5: Possible Alarms |
| |
|
|
|
|
|
| High output | The output voltage is higher than | If the alarm is still active, put the |
|
| voltage (This | the alarm setting. The unit stays in | UPS into bypass by displaying |
|
| alarm is usually | the normal operation mode. If the | the user parameters and |
|
| only listed in the | alarm is not cleared, the unit will | changing “Bypass Operation” to |
|
| events log) | transfer to static bypass operation | “ON.” (See the “Parameter |
|
|
| if bypass is within tolerance. If | Settings” section in this User |
|
|
| bypass is not within tolerance, the | Guide). Then, call APC Global |
|
|
| unit will transfer to | Service. |
|
|
| will not supply output voltage. |
|
|
|
|
|
|
|
| High temp. | The temperature in the main choke | Find the exhaust vents for the |
|
| choke | is too high. If the problem is not | UPS fans and check to see if the |
|
|
| corrected soon, the unit will | fans are operating. Do not try to |
|
|
| transfer to battery operation. | open the unit, and do not insert |
|
|
|
| anything into a fan vent. If the |
|
|
|
| fans are not operating, call APC |
|
|
|
| Global Service. |
|
|
|
|
|
|
| High temp. | The temperature in the main | Find the exhaust vents for the |
|
| transformer | transformer is too high. If the | UPS fans and check to see if the |
|
|
| problem is not corrected soon, the | fans are operating. Do not try to |
|
|
| unit will transfer to | open the unit, and do not insert |
|
|
| will not supply output voltage. | anything into a fan vent. If the |
|
|
|
| fans are not operating, call APC |
|
|
|
| Global Service. |
|
|
|
|
|
|
| Inverter fuse | One or more of the fuses at the | Call APC Global Service. |
|
| blown | output of the inverter are blown |
|
|
|
| (F004, F005, F006). If bypass is |
|
|
|
| within tolerance, the unit transfers |
|
|
|
| to static bypass operation. If not, |
|
|
|
| the unit transfers to |
|
|
|
| does not supply output voltage. |
|
|
|
|
|
|
|
| Inverter voltage | The output voltage is too high or too | If the UPS is in |
|
| error | low. If the alarm was caused by | the UPS by pressing the green |
|
|
| high output voltage, the unit | button inside the door. If the UPS |
|
|
| transfers to static bypass operation | will not restart, a user may have |
|
|
| if bypass is within tolerance. If | started an emergency power off |
|
|
| bypass is not within tolerance, the | (EPO) shutdown. Find out if the |
|
|
| unit transfers to | EPO shut down the UPS; if it did, |
|
|
| not supply output voltage. If the | find out why and make sure the |
|
|
| alarm was caused by low output | emergency situation has passed. |
|
|
| voltage, the unit transfers to static | Then, reset the EPO and restart |
|
|
| bypass operation if bypass is within | the unit by pressing the green |
|
|
| tolerance. If bypass is not within | button inside the door. If the unit |
|
|
| tolerance, the unit transfers to | will still not restart, call APC |
|
|
| battery for five seconds and then | Global Service. |
|
|
| transfers to |
|
|
|
| supplying output voltage. |
|
|
|
|
|
|
|
16 | User Guide APC BC300 Series 40kW 208/450/480V UPS |