Alarms and Events

Table 5: Possible Alarms

Charge reg.

Failure in charge regulation. The

Call APC Global Service.

error (reg. =

unit transfers to battery until the

 

regulator)

“Low DC shutdown” alarm occurs;

 

 

then, it transfers to stand-by and

 

 

does not supply output voltage.

 

 

 

 

External service

The external service bypass switch

Call APC Global Service.

switch activated

is in the line position. The unit is in

 

 

stand-by and does not supply

 

 

output voltage. However, the loads

 

 

may be receiving power from the

 

 

external manual bypass.

 

 

 

 

Fan fault

If the fan monitoring option is

Call APC Global Service.

 

installed, this alarm sounds if one

 

 

or more of the fans are slowing

 

 

down. The unit’s status does not

 

 

change, but the problem may cause

 

 

other high-temperature alarms

 

 

that could change the unit’s status.

 

 

 

 

Fatal Error

Components on the main controller

Call APC Global Service.

RAM1 data

board have failed.

 

error

 

 

 

 

 

Fault in int.

There is a fault in the internal

Call APC Global Service.

power supply

power supply unit (PSU). The UPS

 

 

transfers to stand-by and does not

 

 

supply output voltage.

 

 

 

 

High Battery

The ambient battery temperature

Make sure the room temperature

Temperature

is higher than the set alarm level.

does not exceed 80° F (27° C). If

 

The unit’s status does not change,

so, cool down the room. If the

 

but battery life could be affected.

temperature was below 80° F (27°

 

This alarm is often caused by high

C) at the time of the alarm, find

 

room temperature.

the exhaust vents for the UPS

 

 

fans and check to see if the fans

 

 

are operating. Do not try to open

 

 

the unit, and do not insert

 

 

anything into a fan vent. If the

 

 

fans are not operating, call APC

 

 

Global Service.

 

 

 

High DC

The monitored battery voltage is

Call APC Global Service.

Warning

higher than the unit’s shutdown

 

 

setting.

 

 

 

 

High DC

The monitored battery voltage is

Call APC Global Service.

Shutdown

higher than the unit’s shutdown

 

 

setting. The unit will switch to

 

 

battery power to reduce DC bus

 

 

voltage.

 

 

 

 

 

990-1403

 

 

User Guide APC BC300 Series 40kW 208/450/480V UPS

15

Page 15
Image 15
APC BC300 manual Alarms and Events