
Alarms and Events
Table 5: Possible Alarms
| Output is out of | The output voltage is too high or too | If the UPS is in  | 
| tolerance | low (out of tolerance). If the alarm | the UPS by pressing the green | 
| 
 | was caused by high output voltage, | button inside the door. If the UPS | 
| 
 | the unit transfers to static bypass | will not restart, a user may have | 
| 
 | operation if bypass is within | started an emergency power off | 
| 
 | tolerance. If bypass is not within | (EPO) shutdown. Find out if the | 
| 
 | tolerance, the unit transfers to | EPO shut down the UPS; if it did, | 
| 
 | find out why and make sure the | |
| 
 | output voltage. If the alarm was | emergency situation has passed. | 
| 
 | caused by low output voltage, the | Then, you can reset the EPO and | 
| 
 | unit transfers to static bypass | restart the unit by pressing the | 
| 
 | operation if bypass is within | green button inside the door. If | 
| 
 | tolerance. If bypass is not within | the unit will still not restart, call | 
| 
 | tolerance, the unit transfers to | APC Global Service. | 
| 
 | battery for five seconds and then | 
 | 
| 
 | transfers to  | 
 | 
| 
 | supplying output voltage. | 
 | 
| 
 | 
 | 
 | 
| Overload load is | The unit is loaded with more than | Disconnect equipment connected | 
| over 100% | nominal load on one or more | to the UPS until the load is below | 
| 
 | phases. The UPS status does not | 100%. An electrician must | 
| 
 | change until it can no longer | connect these loads to another | 
| 
 | maintain the correct output | power source. If the alarm | 
| 
 | voltage. Then, the unit transfers to | persists, call APC Global Service. | 
| 
 | static bypass operation if bypass is | 
 | 
| 
 | within tolerance. If not, the unit | 
 | 
| 
 | transfers to battery for five | 
 | 
| 
 | seconds; then, it transfers to stand- | 
 | 
| 
 | by and stops supplying output | 
 | 
| 
 | voltage. | 
 | 
| 
 | 
 | 
 | 
| Static switch 1 | The temperature on the  | Find the vents for the UPS fans | 
| temp. shutdown | for the main static switch is higher | and check to see if the fans are | 
| 
 | than the shutdown level, and the | operating. Do not try to open the | 
| 
 | main static switch has opened. The | unit, and do not insert anything | 
| 
 | unit switches to battery operation. | into a fan vent. If the fans are not | 
| 
 | When the temperature falls below | operating, call APC Global | 
| 
 | the shutdown level, the unit | Service. If the fans are operating, | 
| 
 | transfers back to normal operation. | make sure the room temperature | 
| 
 | If the temperature does not fall to | is below 80° F (27° C). If not, cool | 
| 
 | this level before the “Low DC | down the room. if the room was | 
| 
 | Shutdown” alarm occurs, there will | already below this temperature, | 
| 
 | be no output to the load equipment. | call APC Global Service. | 
| 
 | 
 | 
 | 
| 
 | 
 | 
| 
 | 
 | 
| User Guide APC BC300 Series 40kW 208/450/480V UPS | 19 | 
