Alarms and Events

Table 5: Possible Alarms

Output is out of

The output voltage is too high or too

If the UPS is in stand-by, restart

tolerance

low (out of tolerance). If the alarm

the UPS by pressing the green

 

was caused by high output voltage,

button inside the door. If the UPS

 

the unit transfers to static bypass

will not restart, a user may have

 

operation if bypass is within

started an emergency power off

 

tolerance. If bypass is not within

(EPO) shutdown. Find out if the

 

tolerance, the unit transfers to

EPO shut down the UPS; if it did,

 

stand-by and does not supply

find out why and make sure the

 

output voltage. If the alarm was

emergency situation has passed.

 

caused by low output voltage, the

Then, you can reset the EPO and

 

unit transfers to static bypass

restart the unit by pressing the

 

operation if bypass is within

green button inside the door. If

 

tolerance. If bypass is not within

the unit will still not restart, call

 

tolerance, the unit transfers to

APC Global Service.

 

battery for five seconds and then

 

 

transfers to stand-by and stops

 

 

supplying output voltage.

 

 

 

 

Overload load is

The unit is loaded with more than

Disconnect equipment connected

over 100%

nominal load on one or more

to the UPS until the load is below

 

phases. The UPS status does not

100%. An electrician must

 

change until it can no longer

connect these loads to another

 

maintain the correct output

power source. If the alarm

 

voltage. Then, the unit transfers to

persists, call APC Global Service.

 

static bypass operation if bypass is

 

 

within tolerance. If not, the unit

 

 

transfers to battery for five

 

 

seconds; then, it transfers to stand-

 

 

by and stops supplying output

 

 

voltage.

 

 

 

 

Static switch 1

The temperature on the heat-sink

Find the vents for the UPS fans

temp. shutdown

for the main static switch is higher

and check to see if the fans are

 

than the shutdown level, and the

operating. Do not try to open the

 

main static switch has opened. The

unit, and do not insert anything

 

unit switches to battery operation.

into a fan vent. If the fans are not

 

When the temperature falls below

operating, call APC Global

 

the shutdown level, the unit

Service. If the fans are operating,

 

transfers back to normal operation.

make sure the room temperature

 

If the temperature does not fall to

is below 80° F (27° C). If not, cool

 

this level before the “Low DC

down the room. if the room was

 

Shutdown” alarm occurs, there will

already below this temperature,

 

be no output to the load equipment.

call APC Global Service.

 

 

 

 

990-1403

 

 

User Guide APC BC300 Series 40kW 208/450/480V UPS

19

Page 19
Image 19
APC BC300 manual 990-1403