Specifications

8.0 Specifications

For a complete list of specifications, see the APC BC300 Series Installation Guide.

Table 7: General Specifications

Utility tolerance

+10%, 15% (programmable)

 

 

Bypass tolerance

±10% (programmable)

 

 

Input frequency ±6% (programmable)

60 Hz

 

 

Output frequency

 

- utility synchronized:

60 Hz ±6%

- free running:

60 Hz ±0.1%

 

 

Current distortion

0-5%

 

 

Tolerance

 

- symmetrical load:

±1%, static.

- asymmetrical load:

±3%, static. (100% imbalance, provided

 

output current rating is not exceeded.)

- load step 0-100:

±5%.

 

 

Distortion (linear load)

0-3%

 

 

Overload capacity

 

- normal operation, 1 minute

250%

- normal operation, 10 minutes

150%

- battery operation, 1 minute

150%

- battery operation, 10 minutes

125%

 

 

Audible noise (dBa)

dBa

 

 

Maximum Humidity (non condensing)

95%

 

 

Efficiency

95%

 

 

For Users in the United States Only

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the Installation Guide, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.

990-1403

User Guide APC BC300 Series 40kW 208/450/480V UPS