Specifications
8.0 Specifications
For a complete list of specifications, see the APC BC300 Series Installation Guide.
Table 7: General Specifications
Utility tolerance | +10%, |
|
|
Bypass tolerance | ±10% (programmable) |
|
|
Input frequency ±6% (programmable) | 60 Hz |
|
|
Output frequency |
|
- utility synchronized: | 60 Hz ±6% |
- free running: | 60 Hz ±0.1% |
|
|
Current distortion | |
|
|
Tolerance |
|
- symmetrical load: | ±1%, static. |
- asymmetrical load: | ±3%, static. (100% imbalance, provided |
| output current rating is not exceeded.) |
- load step | ±5%. |
|
|
Distortion (linear load) | |
|
|
Overload capacity |
|
- normal operation, 1 minute | 250% |
- normal operation, 10 minutes | 150% |
- battery operation, 1 minute | 150% |
- battery operation, 10 minutes | 125% |
|
|
Audible noise (dBa) | dBa |
|
|
Maximum Humidity (non condensing) | 95% |
|
|
Efficiency | 95% |
|
|
For Users in the United States Only
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the Installation Guide, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.
User Guide APC BC300 Series 40kW 208/450/480V UPS | 29 |