 | Alarms and Events | |
| 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | Table 5: Possible Alarms | ||
| 
 | 
 | 
 | 
 | |
| 
 | Static switch 1 | The temperature on the  | Find the vents for the UPS fans | |
| 
 | temp. warning | for the main static switch is higher | and check to see if the fans are | |
| 
 | 
 | than the warning setting. The | operating. Do not try to open the | |
| 
 | 
 | unit’s status does not change. | unit, and do not insert anything | |
| 
 | 
 | However, if the temperature | into a fan vent. If the fans are not | |
| 
 | 
 | continues to rise, the unit will | operating, call APC Global | |
| 
 | 
 | sound a “Static switch 1 temp. | Service. If the fans are operating, | |
| 
 | 
 | shutdown” alarm. | make sure the room temperature | |
| 
 | 
 | 
 | is below 80° F (27° C). If not, cool | |
| 
 | 
 | 
 | down the room. if the room was | |
| 
 | 
 | 
 | already below this temperature, | |
| 
 | 
 | 
 | call APC Global Service. | |
| 
 | 
 | 
 | 
 | |
| 
 | Static switch 2 | The temperature on the  | Find the vents for the UPS fans | |
| 
 | temp. shutdown | for the bypass static switch is | and check to see if the fans are | |
| 
 | 
 | higher than the shutdown level and | operating. Do not try to open the | |
| 
 | 
 | the bypass static switch has | unit, and do not insert anything | |
| 
 | 
 | opened. The unit switches to | into a fan vent. If the fans are not | |
| 
 | 
 | battery operation until the | operating, call APC Global | |
| 
 | 
 | temperature falls below the | Service. | |
| 
 | 
 | shutdown level; then, it transfers | If the fans are operating, make | |
| 
 | 
 | back to normal operation. If the | sure the room temperature is | |
| 
 | 
 | temperature does not fall to this | below 80° F (27° C). If not, cool | |
| 
 | 
 | level before the “Low DC | down the room. if the room was | |
| 
 | 
 | shutdown” alarm occurs, there will | already below this temperature, | |
| 
 | 
 | be no output to the load equipment. | call APC Global Service. | |
| 
 | 
 | 
 | 
 | |
| 
 | Static switch 2 | The temperature on the  | Find the vents for the UPS fans | |
| 
 | temp. warning | for the bypass static switch is | and check to see if the fans are | |
| 
 | 
 | higher than the warning setting. | operating. Do not try to open the | |
| 
 | 
 | The unit’s status does not change. | unit, and do not insert anything | |
| 
 | 
 | However, if the temperature | into a fan vent. If the fans are not | |
| 
 | 
 | continues to rise, the unit will | operating, call APC Global | |
| 
 | 
 | sound a “Static switch 2 temp. | Service. | |
| 
 | 
 | shutdown” alarm. | If the fans are operating, make | |
| 
 | 
 | 
 | sure the room temperature is | |
| 
 | 
 | 
 | below 80° F (27° C). If not, cool | |
| 
 | 
 | 
 | down the room. if the room was | |
| 
 | 
 | 
 | already below this temperature, | |
| 
 | 
 | 
 | call APC Global Service. | |
| 
 | 
 | 
 | 
 | |
| 
 | Synchronization | The inverter output is not | If this alarm occurs during the | |
| 
 | error (This | synchronized to the utility (AC | initial  | |
| 
 | alarm occurs | input). The unit will transfer to | must check the phase rotation. | |
| 
 | during a power | battery operation until the “Low | If this alarm occurs while the unit | |
| 
 | outage) | DC shutdown” alarm sounds. If the | is connected to a generator, the | |
| 
 | 
 | unit can synchronize to utility | unit may be having problems | |
| 
 | 
 | again before this event occurs, it | synchronizing to the generator. | |
| 
 | 
 | will transfer back to normal | Call APC Global Service. | |
| 
 | 
 | operation. | If the alarm does not occur during | |
| 
 | 
 | 
 | the initial  | |
| 
 | 
 | 
 | not connected to a generator, call | |
| 
 | 
 | 
 | APC Global Service. | |
| 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | |