Alarms and Events

 

 

 

 

 

 

 

 

 

 

 

Table 5: Possible Alarms

 

 

 

 

 

Static switch 1

The temperature on the heat-sink

Find the vents for the UPS fans

 

temp. warning

for the main static switch is higher

and check to see if the fans are

 

 

than the warning setting. The

operating. Do not try to open the

 

 

unit’s status does not change.

unit, and do not insert anything

 

 

However, if the temperature

into a fan vent. If the fans are not

 

 

continues to rise, the unit will

operating, call APC Global

 

 

sound a “Static switch 1 temp.

Service. If the fans are operating,

 

 

shutdown” alarm.

make sure the room temperature

 

 

 

is below 80° F (27° C). If not, cool

 

 

 

down the room. if the room was

 

 

 

already below this temperature,

 

 

 

call APC Global Service.

 

 

 

 

 

Static switch 2

The temperature on the heat-sink

Find the vents for the UPS fans

 

temp. shutdown

for the bypass static switch is

and check to see if the fans are

 

 

higher than the shutdown level and

operating. Do not try to open the

 

 

the bypass static switch has

unit, and do not insert anything

 

 

opened. The unit switches to

into a fan vent. If the fans are not

 

 

battery operation until the

operating, call APC Global

 

 

temperature falls below the

Service.

 

 

shutdown level; then, it transfers

If the fans are operating, make

 

 

back to normal operation. If the

sure the room temperature is

 

 

temperature does not fall to this

below 80° F (27° C). If not, cool

 

 

level before the “Low DC

down the room. if the room was

 

 

shutdown” alarm occurs, there will

already below this temperature,

 

 

be no output to the load equipment.

call APC Global Service.

 

 

 

 

 

Static switch 2

The temperature on the heat-sink

Find the vents for the UPS fans

 

temp. warning

for the bypass static switch is

and check to see if the fans are

 

 

higher than the warning setting.

operating. Do not try to open the

 

 

The unit’s status does not change.

unit, and do not insert anything

 

 

However, if the temperature

into a fan vent. If the fans are not

 

 

continues to rise, the unit will

operating, call APC Global

 

 

sound a “Static switch 2 temp.

Service.

 

 

shutdown” alarm.

If the fans are operating, make

 

 

 

sure the room temperature is

 

 

 

below 80° F (27° C). If not, cool

 

 

 

down the room. if the room was

 

 

 

already below this temperature,

 

 

 

call APC Global Service.

 

 

 

 

 

Synchronization

The inverter output is not

If this alarm occurs during the

 

error (This

synchronized to the utility (AC

initial start-up, an electrician

 

alarm occurs

input). The unit will transfer to

must check the phase rotation.

 

during a power

battery operation until the “Low

If this alarm occurs while the unit

 

outage)

DC shutdown” alarm sounds. If the

is connected to a generator, the

 

 

unit can synchronize to utility

unit may be having problems

 

 

again before this event occurs, it

synchronizing to the generator.

 

 

will transfer back to normal

Call APC Global Service.

 

 

operation.

If the alarm does not occur during

 

 

 

the initial start-up and the UPS is

 

 

 

not connected to a generator, call

 

 

 

APC Global Service.

990-1403

 

 

 

 

 

 

 

 

 

 

 

 

20

User Guide APC BC300 Series 40kW 208/450/480V UPS

 

Page 20
Image 20
APC BC300 manual Alarms and Events