| Alarms and Events | |
|
|
|
| |
|
|
|
|
|
|
| Table 5: Possible Alarms | ||
|
|
|
| |
| Static switch 1 | The temperature on the | Find the vents for the UPS fans | |
| temp. warning | for the main static switch is higher | and check to see if the fans are | |
|
| than the warning setting. The | operating. Do not try to open the | |
|
| unit’s status does not change. | unit, and do not insert anything | |
|
| However, if the temperature | into a fan vent. If the fans are not | |
|
| continues to rise, the unit will | operating, call APC Global | |
|
| sound a “Static switch 1 temp. | Service. If the fans are operating, | |
|
| shutdown” alarm. | make sure the room temperature | |
|
|
| is below 80° F (27° C). If not, cool | |
|
|
| down the room. if the room was | |
|
|
| already below this temperature, | |
|
|
| call APC Global Service. | |
|
|
|
| |
| Static switch 2 | The temperature on the | Find the vents for the UPS fans | |
| temp. shutdown | for the bypass static switch is | and check to see if the fans are | |
|
| higher than the shutdown level and | operating. Do not try to open the | |
|
| the bypass static switch has | unit, and do not insert anything | |
|
| opened. The unit switches to | into a fan vent. If the fans are not | |
|
| battery operation until the | operating, call APC Global | |
|
| temperature falls below the | Service. | |
|
| shutdown level; then, it transfers | If the fans are operating, make | |
|
| back to normal operation. If the | sure the room temperature is | |
|
| temperature does not fall to this | below 80° F (27° C). If not, cool | |
|
| level before the “Low DC | down the room. if the room was | |
|
| shutdown” alarm occurs, there will | already below this temperature, | |
|
| be no output to the load equipment. | call APC Global Service. | |
|
|
|
| |
| Static switch 2 | The temperature on the | Find the vents for the UPS fans | |
| temp. warning | for the bypass static switch is | and check to see if the fans are | |
|
| higher than the warning setting. | operating. Do not try to open the | |
|
| The unit’s status does not change. | unit, and do not insert anything | |
|
| However, if the temperature | into a fan vent. If the fans are not | |
|
| continues to rise, the unit will | operating, call APC Global | |
|
| sound a “Static switch 2 temp. | Service. | |
|
| shutdown” alarm. | If the fans are operating, make | |
|
|
| sure the room temperature is | |
|
|
| below 80° F (27° C). If not, cool | |
|
|
| down the room. if the room was | |
|
|
| already below this temperature, | |
|
|
| call APC Global Service. | |
|
|
|
| |
| Synchronization | The inverter output is not | If this alarm occurs during the | |
| error (This | synchronized to the utility (AC | initial | |
| alarm occurs | input). The unit will transfer to | must check the phase rotation. | |
| during a power | battery operation until the “Low | If this alarm occurs while the unit | |
| outage) | DC shutdown” alarm sounds. If the | is connected to a generator, the | |
|
| unit can synchronize to utility | unit may be having problems | |
|
| again before this event occurs, it | synchronizing to the generator. | |
|
| will transfer back to normal | Call APC Global Service. | |
|
| operation. | If the alarm does not occur during | |
|
|
| the initial | |
|
|
| not connected to a generator, call | |
|
|
| APC Global Service. | |
|
|
|
| |
|
|
|
| |
|
|
|
| |
20 | User Guide APC BC300 Series 40kW 208/450/480V UPS |
|