Argosy Research H-125 Series owner manual 001 MIN, 300 MIN, Regen, Time, Gallons

Models: H-125 Series

1 40
Download 40 pages 39.84 Kb
Page 11
Image 11
REGEN

DELAY + IMMEDIATE Step 12S

SET

REGEN

 

 

 

RELAY 1 TRIGGER

Step 13S

SET

TIME

 

 

 

 

 

RELAY 1 SET POINT

Step 14S

SET

10

MIN

 

 

 

RELAY 1 DURATION

Step 15S

SET

3:00 MIN

 

 

RELAY 1 TRIGGER

 

SET

GALLONS

 

 

RELAY 1 SETPOINT

Step 16S

SET

1 GAL

STEP 12 S – Set Regeneration Time Options using the or button. If value is set to:

“DELAY” means regeneration will occur at the preset time; (page 8, step 4)

“IMMEDIATE” means regeneration will occur immediately when the gallons capacity reaches 0 (zero); or

“DELAY + IMMEDIATE” means regeneration will occur at one of the following:

-the preset time when the gallons capacity falls below the reserve or the specified number of days between regenerations is reached, whichever comes first; or

-immediately after 10 minutes of no water usage when the gallon capacity reaches 0 (zero).

See page 34 for more options. Factory Setting is DELAY + IMMEDIATE. Press NEXT to go to Step 13S. Press REGEN to return to previous step.

STEP 13 S – Set Relay to activate by Time or Gallons, REGEN GALLONS or OFF by using or buttons. A relay can be used to operate a chemical feed pump or solenoid. The choices are:

Relay Triggered on Time - Relay activates after set number of minutes after start of regenera- tion. Start of regeneration is defined by first backwash cycle, dn brine or up brine, whichever is first. Relay deactivates after set time.

Relay Triggered on Gallons - Relay activates every set number of gallons while in service and deactivates after set time.

Regen Gallons - Relay activates after set number of gallons in service and if any water is used during regeneration and de-activates after set time or when meter stops registering flow, whichever comes first.

Off - If off is selected, Steps 14S or 15S will not be shown. Factory setting = OFF. Press NEXT to go to step 14S or 15S for relay settings, or 20S if OFF selected.

STEP 14 S – If off was selected in previous step, this screen does not appear.

If Time chosen to Activate Relay, use up and down arrows to set # of minutes AFTER START OF REGEN to activate relay. Press NEXT.

Start of regeneration is defined as first Backwash or Regenerant Draw.

STEP 15 S – Use Up and Down arrows to set duration of relay activation in minutes.

Time Range = 1 second - 500 minutes. Press NEXT to go to Step 20S. Press REGEN to return to previous step.

Gallons Chosen to Activate Relay, This screen indicated gallons chosen to activate relay. If Off or Time was selected in previous steps, this screen does not appear. Press NEXT to select number of gallons per relay activation.

STEP 16 S – use up and down arrows to set # of gallons per relay activation. Range = 1-100 gallons. Press NEXT to select duration of relay activation.

 

 

 

 

 

 

 

 

RELAY 1 DURATION

 

SET

0:01 MIN

 

Step 17S

STEP 17 S – Use up and down arrows to set duration of relay activation in minutes. Range = 1 second - 500 minutes. Press NEXT to go to Step 20S. Press REGEN to return to previous step.

Figure 12b

11

Page 11
Image 11
Argosy Research H-125 Series owner manual 001 MIN, 300 MIN, Regen, Time, Gallons