Operation | |
|
|
4.2.7 Measuring the Leak Rate
After finding a leak, a measurement can be made to determine its leak rate as follows:
1.Press the MODE button to display “MERS” at the bottom of the Data Display screen or “MEASR” on the Smart probe.
2.Allow the instrument to sample fresh air. The gas reading must be “0.00” before proceeding. If necessary, press the ZERO button to zero the reading while sampling fresh air.
3.While observing the gas reading, hold the probe tip over the leak source until the reading stabilizes. In the examples below, a leak rate of 2.80 Oz/yr of R134a is being measured.
Instrument Display
Oz/yr
R134A
SETUP
SM MERS
Smart Probe Display
2.80SM MEASR(1)
4.2.8 Measuring the PPM Level
The
NOTE: Although the
1.Set up the instrument’s Leak Units to ppm as described in Section 2.4.2 Leak Units.
2.Press the MODE button to display “MERS” at the bottom of the Data Display screen or “MEASR” on the Smart probe.
3.Allow the instrument to sample fresh air. The gas reading must be “00.0” before proceeding. Press the ZERO button to zero the gas reading while sampling fresh air.
4.Place probe in area to be measured. In the example below, 38.0 ppm of R134a is being measured. Note that the display is auto ranging, causing the decimal point to turn off above 99.9 ppm.
Instrument Display
ppm
R134A
SETUP
SM MERS
Smart Probe Display
38.0SM MEASR(1)
32 | Instruction |