Specifications | |
|
|
7 Specifications
Gases Detected | Detects and measures, depending on instrument’s part number: |
| • CFCs, HCFCs, HFCs and Halogens |
| R11, R12, R22, R23, R113, R114, R123, R124, R134a, R227, R236fa, |
| R401A, R402A, R402A, R404A, R407A, R407C, R408A, R409A, R410A, |
| R500, R502, R503, R507, R508B, H1211, H1301, H2402, N1230, FA188 |
| • R600a |
| • SF6 |
| • CO2 |
| • R227 |
Detection Method | Infrared |
Measurement Units | oz/yr, g/yr, mL/s, PaM3/s, ppm |
Measurement Range | 0.03 to 5.00 oz/yr |
| 0.85 to 142 g/yr |
| 0.08 x |
| 0.08 x |
| 0 to 1,000 ppm |
Operating Modes | Search: detects presence and location of gas leaks |
| Measure: calculates and displays leak rate |
Response Time | 0.5 to 1 second (dependent on |
Sensitivity | 0.03 oz/yr (0.9 g/yr) all gases |
Resolution | 0.01 oz/yr (0.1 g/yr) |
Accuracy: |
|
Leak Rate | ±1% of the accuracy value marked on tag attached to leak source |
PPM | ±10% of reading (can be improved to ±1% if recalibrated using a known |
| concentration of refrigerant gas) |
Temperature Drift | ±0.8% of reading per °C |
Calibration | Internal: calibration performed using the unit’s |
| External: calibration performed using a customer supplied leak |
| source of a known gas type and leak rate |
Relays | Four SPDT relays (rated 3 A, 240 VAC), each programmable to energize |
| under 11 different operating conditions |
Audio Speaker | Audible indication of leak level |
AC Power | 100 to 240 VAC, 50/60 Hz |
Power Consumption | 15 Watts |
2 minutes (30 minutes to meet published specifications) | |
Operating Temperature | 32 to 122 °F (0 to 50 °C) |
Storage Temperature | −4 to 122 °F (−20 to 50 °C) |
Ambient Humidity | 5 to 90% RH, |
Dimensions | 4 x 10.75 x 15.5 in. |
| (101.6 x 273.1 x 393.7 mm) |
Weight | 18 lb (8.2 kg) |
Instruction | 51 |