Bay Technical Associates V80 PDI-2, V79 PDI-1 owner manual 115,1 1320 11/18/93

Models: V80 PDI-2 V79 PDI-1

1 49
Download 49 pages 39.29 Kb
Page 22
Image 22

The following examples show the messages received using data commands where the PDI is installed in Unit 1 Module 15 with time tagging enabled. If you select the module and issue the RD1<cr> command (Report Event Duration for Channel 1), the module will respond with a single message showing the Event Duration for Channel 1 similar to the following:

1:15,1 1320 11/18/93 09:12:22

where 1:15,1 represents Unit 1/Module 15/Channel 1, 1320 indicates the event duration is 1320 milliseconds, and 11/18/93 09:12:22 is the time tag.

If you issue the RC1<cr> command (Report Event Counter for Channel 1), the module will respond with a message showing the Event Counter similar to the following:

1:15,1 823 11/18/93 09:12:22

where 1:15,1 represents Unit 1/Module 15/Channel 1, 823 indicates the number of recorded events is 823 times, and 11/18/93 09:12:22 is the time tag.

If you issue the RS1<cr> command (Report Single Buffered Event for Channel 1), the module will respond with a message showing the input status for Channel 1 similar to the following:

1:15,1 1 11/18/93 09:12:22

where 1:15,1 represents Unit 1/Module 15/Channel 1, 1 indicates the first buffered sample for Channel 1 is closed (PDI-1) or has voltage applied (PDI-2), and 11/18/93 09:12:22 is the time tag.

18

Page 22
Image 22
Bay Technical Associates V80 PDI-2, V79 PDI-1 owner manual 115,1 1320 11/18/93