These optically isolated inputs provide an efficient means for the monitoring of external process and control functions. All functions provided by the board are programmable through a series of detailed configuration menus. Additional functionality is made available through the use of BayTech or user provided application software. Input connections to the PDI-2 are made through a standard DC-37F connector.

2 SPECIFICATIONS

2.1V79 PDI-1 SWITCH INPUT STATUS MODULE

(typical for 25o C unless otherwise noted)

INPUTS: 16 with individual ground returns or common (single-point) ground.

DRIVE DISTANCE: Up to 1000 Ohms cable resistance, for

example: AWG 36 - 2400 ft., AWG 24 - 15000 ft., AWG 22 - 62000 ft.

POWER REQUIREMENTS: +5VDC, 40 ma typical (provided by M16/M8 pwr supply).

DEBOUNCE: 0 to 60000 ms (software selectable).

ENVIRONMENTAL:

Operating temperature range: 0o to 70o C

Storage temperature range: -40oto 85o C

Humidity: 5% to 95% non-condensing