PRESSURE REGULATION AND TESTING

Installation Gas Connection 2” (51 mm)

Gas Connection

PRESSURE REGULATION AND TESTING

Each oven has been adjusted at the factory to op- erate with the type of gas specified on the rating plate attached to the left side of the control panel.

Each oven is supplied with a regulator to maintain the proper gas pressure. The regulator is essen- tial to the proper operation of the oven and should not be removed. It is preset to provide the oven with 3.5” W.C. (0.87 kPa) while the flame is on. The regulator is located on top of the gas valve, between the manual shutoff and solenoid valves.

DO NOT INSTALL AN ADDITIONAL REGULATOR WHERE THE OVEN CONNECTS TO THE GAS SUPPLY UNLESS THE SUPPLY EXCEEDS THE MAXIMUM.

NOTE: The maximum gas supply pressure to the oven is 10.5” W.C. (2.61 kPa). The mini- mum gas supply pressure to the oven is 4.5” W.C. (1.1 kPa).

Installation must conform with local codes, or in the absence of local codes, with the National Fuel Gas Code, NFPA54/ANSI Z223.1 ---Latest Edition, the Natural Gas Installation Code CAN/CGA- B149.1 or the Propane Installation Code, CAN/ CGA-B149.2as applicable.

The oven and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.45kPa).

The oven must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas piping system at test pressures equal or less than 1/2 psig (3.45kPa).