AutoDome Modular Camera System

Troubleshooting en 35

 

 

3.4.2BILINX

Ensure that only one BILINX device is connected to the PC. For example, only one VP-USB may be connected to a PC at one time. In addition, disconnect the video output from the AutoDome from any other BILINX controller during a firmware upgrade.

Confirm that all connections are correct and that the maximum recommended distance has not been exceeded.

Confirm that there is a direct coax connection to the dome. BILINX cannot be transmitted through fiber without special fiber modules. BILINX also cannot be passed through analog distribution amplifiers, with the exception to the Bosch LTC 5231/90 and

LTC 5234/90.

Confirm that the coax signal is correctly terminated with only one 75 ohm load.

3.4.3

Serial (RS232 or RS485)

 

– Ensure that the CPU switch is set to the correct format. The factory default setting is

 

RS485. Refer to the AutoDome Modular Camera System Installation Manual for more

 

information.

 

– Confirm that the correct COM port was selected and that the cable is connected firmly to

 

the DB9 connector.

 

– Ensure that all connections are correct and that the maximum recommended distance

 

has not been exceeded.

 

– Ensure that the RS232 GROUND connection has been used.

 

– If using RS485, ensure that the termination resistor has been installed.

 

– Ensure the AutoDome AutoBaud is turned on.

3.4.4Firmware Upgrade via CTFID Fails

Try to repeat the upgrade a second time. If the upgrade continues to fail, contact Bosch tech- nical support.

Bosch Security Systems, Inc.

Firmware Update Manual

F.01U.097.269 1.06 2011.09

Page 39
Image 39
Bosch Appliances VG4 manual Serial RS232 or RS485, 4Firmware Upgrade via Ctfid Fails