Bryant 548F, 549B manual Performance Data, 542J150,180, Cooling Capacities, Bypass

Models: 549B 548F 542J

1 122
Download 122 pages 32.45 Kb
Page 109
Image 109
BYPASS

PERFORMANCE DATA

COOLING CAPACITIES

542J150

Temp (F)

 

 

 

 

 

 

 

 

 

Air Entering Indoor Coil — Cfm/BF

 

 

 

 

 

 

 

 

 

Air Ent

 

3750/0.04

 

 

4500/0.05

 

 

5000/0.05

 

 

5625/0.06

 

 

6250/0.07

 

Outdoor

 

 

 

 

 

 

 

 

 

Air Entering Indoor Coil — Ewb (F)

 

 

 

 

 

 

 

 

 

 

Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

 

67

 

62

72

 

67

 

62

72

 

67

 

62

72

 

67

 

62

72

 

67

 

62

 

 

 

 

 

 

 

 

 

 

 

 

 

75

 

TC

167.0

 

154.0

 

140.0

171.0

 

158.0

 

144.0

173.0

 

159.0

 

146.0

171.0

 

162.0

 

148.0

173.0

 

161.0

 

151.0

 

SHC

79.6

 

100.0

 

120.0

85.0

 

108.0

 

131.0

87.5

 

114.0

 

138.0

94.5

 

120.0

 

146.0

97.7

 

127.0

 

150.0

 

 

kW

10.00

 

9.77

 

9.50

10.10

 

9.87

 

9.61

10.20

 

9.93

 

9.68

10.20

 

10.00

 

9.74

10.20

 

10.00

 

9.80

85

 

TC

160.0

 

148.0

 

133.0

164.0

 

151.0

 

137.0

167.0

 

154.0

 

140.0

168.0

 

155.0

 

143.0

166.0

 

157.0

 

146.0

 

SHC

77.6

 

98.9

 

118.0

82.0

 

107.0

 

129.0

86.1

 

113.0

 

136.0

89.6

 

118.0

 

142.0

95.3

 

125.0

 

146.0

 

 

kW

11.10

 

10.80

 

10.40

11.20

 

10.90

 

10.60

11.30

 

11.00

 

10.70

11.30

 

11.00

 

10.80

11.30

 

11.10

 

10.80

95

 

TC

155.0

 

141.0

 

127.0

157.0

 

144.0

 

131.0

160.0

 

146.0

 

133.0

161.0

 

149.0

 

137.0

163.0

 

149.0

 

140.0

 

SHC

76.1

 

96.3

 

115.0

80.3

 

105.0

 

126.0

84.4

 

110.0

 

132.0

86.5

 

117.0

 

137.0

91.7

 

121.0

 

140.0

 

 

kW

12.20

 

11.80

 

11.40

12.20

 

11.90

 

11.50

12.40

 

12.00

 

11.60

12.40

 

12.10

 

11.80

12.50

 

12.10

 

11.90

105

 

TC

147.0

 

133.0

 

120.0

150.0

 

137.0

 

124.0

152.0

 

138.0

 

127.0

153.0

 

140.0

 

131.0

154.0

 

141.0

 

134.0

 

SHC

73.6

 

93.3

 

112.0

78.5

 

102.0

 

123.0

81.6

 

108.0

 

127.0

85.1

 

114.0

 

131.0

88.6

 

120.0

 

134.0

 

 

kW

13.20

 

12.70

 

12.30

13.30

 

12.90

 

12.50

13.40

 

13.00

 

12.60

13.50

 

13.10

 

12.80

13.50

 

13.10

 

12.90

115

 

TC

140.0

 

126.0

 

112.0

141.0

 

129.0

 

118.0

144.0

 

130.0

 

121.0

144.0

 

131.0

 

125.0

146.0

 

133.0

 

128.0

 

SHC

71.4

 

90.3

 

109.0

75.1

 

99.1

 

117.0

78.9

 

104.0

 

121.0

81.9

 

110.0

 

125.0

87.0

 

117.0

 

128.0

 

 

kW

14.20

 

13.70

 

13.20

14.30

 

13.90

 

13.50

14.40

 

14.00

 

13.70

14.50

 

14.00

 

13.90

14.60

 

14.10

 

14.00

125

 

TC

131.0

 

118.0

 

105.0

134.0

 

120.0

 

111.0

135.0

 

122.0

 

115.0

137.0

 

123.0

 

118.0

136.0

 

124.0

 

121.0

 

SHC

68.1

 

87.6

 

105.0

73.5

 

96.4

 

111.0

75.7

 

102.0

 

115.0

80.7

 

108.0

 

118.0

83.4

 

113.0

 

121.0

 

 

kW

15.20

 

14.70

 

14.10

15.40

 

14.90

 

14.50

15.40

 

14.90

 

14.70

15.60

 

15.00

 

14.90

15.60

 

15.10

 

15.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

542J180

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

 

 

 

 

Air Entering Indoor Coil — Cfm/BF

 

 

 

 

 

 

 

 

 

Air Ent

 

4500/0.06

 

 

5250/0.08

 

 

6000/0.10

 

 

6750/0.10

 

 

7500/0.12

 

Outdoor

 

 

 

 

 

 

 

 

 

Air Entering Indoor Coil — Ewb (F)

 

 

 

 

 

 

 

 

 

 

Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

 

67

 

62

72

 

67

 

62

72

 

67

 

62

72

 

67

 

62

72

 

67

 

62

 

 

 

 

 

 

 

 

 

 

 

 

 

75

 

TC

210.0

 

192.0

 

173.4

216.0

 

196.6

 

178.4

220.0

 

202.0

 

182.2

222.0

 

204.0

 

185.6

224.0

 

206.0

 

190.2

 

SHC

100.6

 

125.2

 

148.2

106.0

 

134.0

 

160.6

110.6

 

143.0

 

172.2

115.0

 

151.2

 

183.2

120.2

 

158.2

 

190.0

 

 

kW

13.58

 

13.12

 

12.66

13.76

 

13.28

 

12.84

13.88

 

13.44

 

12.98

13.96

 

13.52

 

13.10

14.02

 

13.60

 

13.26

85

 

TC

202.0

 

183.0

 

164.4

208.0

 

187.8

 

169.0

212.0

 

191.4

 

172.8

212.0

 

194.0

 

177.2

214.0

 

195.8

 

182.2

 

SHC

98.0

 

121.8

 

144.2

103.8

 

131.2

 

156.4

109.0

 

140.0

 

168.6

112.0

 

148.0

 

177.0

116.2

 

155.6

 

182.2

 

 

kW

14.86

 

14.32

 

13.78

15.08

 

14.52

 

13.98

15.22

 

14.66

 

14.14

15.26

 

14.78

 

14.30

15.34

 

14.86

 

14.50

95

 

TC

192.4

 

173.2

 

155.0

196.2

 

177.8

 

159.2

200.0

 

180.8

 

163.4

202.0

 

183.4

 

169.0

204.0

 

185.4

 

174.2

 

SHC

94.8

 

118.0

 

140.0

100.2

 

127.4

 

152.6

105.6

 

136.4

 

163.4

110.6

 

144.8

 

169.0

114.2

 

153.2

 

173.8

 

 

kW

16.16

 

15.52

 

14.88

16.32

 

15.72

 

15.10

16.48

 

15.88

 

15.30

16.62

 

16.00

 

15.54

16.64

 

16.12

 

15.76

105

 

TC

182.0

 

163.0

 

145.0

186.4

 

167.0

 

149.4

188.6

 

170.0

 

155.4

191.0

 

172.2

 

160.8

193.0

 

173.8

 

165.2

 

SHC

91.0

 

114.2

 

135.2

96.8

 

123.6

 

147.6

101.8

 

132.6

 

155.2

107.2

 

141.2

 

160.6

112.2

 

149.6

 

165.2

 

 

kW

17.36

 

16.64

 

15.92

17.58

 

16.86

 

16.16

17.70

 

17.04

 

16.48

17.84

 

17.18

 

16.74

17.94

 

17.28

 

16.96

115

 

TC

171.2

 

152.4

 

134.8

175.0

 

156.2

 

140.6

177.8

 

158.8

 

146.8

179.4

 

160.8

 

152.2

179.6

 

162.2

 

156.4

 

SHC

87.4

 

110.2

 

130.8

92.6

 

119.4

 

140.6

98.8

 

128.2

 

146.8

103.6

 

136.8

 

151.8

107.2

 

144.6

 

156.2

 

 

kW

18.54

 

17.72

 

16.90

18.76

 

17.94

 

17.24

18.94

 

18.12

 

17.60

19.02

 

18.28

 

17.90

19.04

 

18.38

 

18.16

125

 

TC

159.4

 

141.2

 

125.0

162.8

 

143.8

 

132.0

165.6

 

147.0

 

137.8

166.6

 

148.8

 

143.0

168.2

 

150.0

 

146.8

 

SHC

83.6

 

105.8

 

125.0

89.0

 

115.0

 

131.8

94.4

 

123.6

 

137.8

99.8

 

132.2

 

142.8

105.0

 

139.6

 

146.6

 

 

kW

19.64

 

18.74

 

17.88

19.86

 

19.00

 

18.34

20.00

 

19.12

 

18.72

20.20

 

19.28

 

19.00

20.20

 

19.40

 

19.28

LEGEND

BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb

kW — Compressor Motor Power Input

SHC — Gross Sensible Heat Capacity (1000 Btuh) TC — Gross Total Capacity (1000 Btuh)

NOTES:

1.Direct interpolation is permissible. Do not extrapolate.

2.The following formulas may be used:

sensible capacity (Btuh)

tldb = tedb

1.10 x cfm

tlwb = Wet-bulb temperature corresponding to enthalpy of air leav- ing indoor coil (hlwb)

total capacity (Btuh)

hlwb = hewb

4.5 x cfm

Where: hewb = Enthalpy of air entering indoor coil

3.SHC is based on 80 F edb temperature of air entering indoor coil. Below 80 F edb, subtract (corr factor x cfm) from SHC.

Above 80 F edb, add (corr factor x cfm) to SHC.

BYPASS

 

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

 

under 75

FACTOR

 

81

82

83

84

85

 

over 85

(BF)

 

 

 

 

Correction Factor

 

.05

1.04

2.07

3.11

4.14

5.18

 

 

.10

.98

1.96

2.94

3.92

4.90

 

Use formula

.20

.87

1.74

2.62

3.49

4.36

 

shown below.

.30

.76

1.53

2.29

3.05

3.82

 

 

Interpolation is permissible.

Correction Factor = 1.10 x (1 – BF) x (edb – 80).

542J150,180

109

Page 109
Image 109
Bryant 548F, 549B manual Performance Data, 542J150,180, Cooling Capacities, Bypass, Entering Air Dry-Bulbtemp F