Bryant 549B, 542J, 548F PERFORMANCE DATA cont, FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS cont

Models: 549B 548F 542J

1 122
Download 122 pages 32.45 Kb
Page 86
Image 86
Manual background

PERFORMANCE DATA (cont)

FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)

 

 

 

549B090 (71/2 TONS) — STANDARD MOTOR (BELT DRIVE)

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

 

0.2

 

0.4

 

0.6

 

 

0.8

 

1.0

 

 

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

 

Rpm

 

Bhp

Rpm

 

Bhp

 

 

 

2250

465

 

0.43

554

 

0.64

630

 

0.86

 

695

 

1.09

757

 

1.34

 

 

 

2300

471

 

0.45

559

 

0.66

635

 

0.89

 

699

 

1.12

760

 

1.37

 

 

 

2400

482

 

0.50

569

 

0.71

645

 

0.95

 

708

 

1.18

768

 

1.44

 

 

 

2500

494

 

0.54

581

 

0.76

654

 

1.01

 

717

 

1.25

776

 

1.51

 

 

 

2550

501

 

0.57

587

 

0.79

659

 

1.05

 

722

 

1.29

780

 

1.55

 

 

 

2600

507

 

0.59

592

 

0.82

663

 

1.08

 

727

 

1.32

784

 

1.58

 

 

 

2700

520

 

0.65

604

 

0.89

672

 

1.14

 

737

 

1.40

793

 

1.66

 

 

 

2800

533

 

0.71

615

 

0.95

683

 

1.20

 

747

 

1.49

802

 

1.75

 

 

 

2900

546

 

0.77

626

 

1.02

693

 

1.27

 

756

 

1.57

813

 

1.84

 

 

 

3000

559

 

0.83

637

 

1.09

704

 

1.35

 

765

 

1.66

823

 

1.94

 

 

 

3100

572

 

0.90

648

 

1.17

715

 

1.43

 

775

 

1.74

832

 

2.05

 

 

 

3200

585

 

0.96

660

 

1.24

727

 

1.52

 

785

 

1.83

841

 

2.15

 

 

 

3300

598

 

1.03

671

 

1.32

739

 

1.62

 

795

 

1.91

851

 

2.26

 

 

 

3400

610

 

1.10

682

 

1.41

750

 

1.72

 

806

 

2.01

860

 

2.36

 

 

 

3500

623

 

1.17

694

 

1.50

761

 

1.82

 

817

 

2.11

870

 

2.47

 

120-549B036

 

3600

636

 

1.25

707

 

1.60

772

 

1.93

 

828

 

2.23

880

 

2.57

 

 

3700

649

 

1.33

720

 

1.71

783

 

2.03

 

840

 

2.35

890

 

2.69

 

 

 

3750

655

 

1.37

727

 

1.77

789

 

2.09

 

846

 

2.42

896

 

2.75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

549B090 (71/2 TONS) — STANDARD MOTOR (BELT DRIVE) (cont)

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

 

1.2

 

1.4

 

1.6

 

 

1.8

 

2.0

 

 

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

 

Rpm

 

Bhp

Rpm

 

Bhp

 

 

 

2250

810

 

1.62

850

 

1.91

873

 

2.20

 

890

 

2.50

903

 

2.78

 

 

 

2300

816

 

1.65

859

 

1.94

888

 

2.24

 

897

 

2.55

922

 

2.85

 

 

 

2400

824

 

1.72

872

 

2.01

909

 

2.32

 

931

 

2.64

935

 

2.96

 

 

 

2500

832

 

1.79

882

 

2.09

925

 

2.40

 

955

 

2.72

972

 

3.06

 

 

 

2550

836

 

1.83

887

 

2.13

931

 

2.45

 

964

 

2.77

986

 

3.11

 

 

 

2600

839

 

1.87

891

 

2.17

936

 

2.49

 

973

 

2.82

999

 

3.16

 

 

 

2700

846

 

1.95

898

 

2.26

946

 

2.58

 

 

 

 

1019

 

3.26

 

 

 

 

987

 

2.91

 

 

 

 

2800

855

 

2.04

906

 

2.35

954

 

2.67

 

997

 

3.01

1034

 

3.36

 

 

 

2900

863

 

2.13

913

 

2.44

961

 

2.77

 

1006

 

3.12

 

 

 

 

3000

872

 

2.22

921

 

2.54

969

 

2.88

 

1014

 

3.22

 

 

 

 

3100

882

 

2.33

930

 

2.65

 

 

 

 

1021

 

3.34

 

 

 

 

976

 

2.99

 

 

 

 

 

 

3200

892

 

2.45

939

 

2.76

984

 

3.10

 

 

 

 

 

 

3300

902

 

2.57

948

 

2.88

993

 

3.21

 

 

 

 

 

 

3400

912

 

2.69

 

 

 

1002

 

3.34

 

 

 

 

 

 

958

 

3.01

 

 

 

 

 

 

 

3500

921

 

2.82

968

 

3.15

 

 

 

 

 

 

 

3600

 

 

 

978

 

3.29

 

 

 

 

 

 

 

930

 

2.95

 

 

 

 

 

 

 

3700

940

 

3.07

 

 

 

 

 

 

 

 

3750

945

 

3.14

 

 

 

 

 

LEGEND

Bhp — Brake Horsepower Input to Fan

Refer to page 87 for general Fan Performance notes.

NOTES:

1. Boldface indicates a field-supplied drive is required. (See Note 4.)

2.Manual background indicates field-supplied motor and drive are required.

3.Maximum continuous bhp is 2.90.

4.Standard motor drive range: 725 to 925 rpm. All other rpms require field-supplied drive.