548F036-120

PERFORMANCE DATA (cont)

ACCESSORY/FIOP STATIC PRESSURE* (in. wg) — 548F036-072

COMPONENT

 

 

 

 

 

CFM

 

 

 

 

900

1200

1400

1600

1800

 

2000

2200

2400

2600

3000

 

 

1 Heater Module

0.05

0.07

0.09

0.09

0.10

 

0.11

0.11

0.12

0.13

0.15

2 Heater Modules

0.15

0.16

0.16

0.16

0.17

 

0.17

0.17

0.18

0.18

0.19

Durablade Economizer

0.05

0.05

0.05

0.05

0.05

 

0.05

0.05

0.05

0.05

0.05

Accessory

 

 

 

 

 

 

 

 

 

 

 

 

EconoMi$er

0.05

0.09

0.13

0.17

0.22

 

0.27

0.32

0.39

0.45

0.53

LEGEND

FIOP — Factory-Installed Option

*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance tables to deter- mine blower rpm and watts.

ACCESSORY/FIOP STATIC PRESSURE* (in. wg) — 548F090-120

COMPONENT

 

 

 

 

 

CFM

 

 

 

 

2250

2500

3000

3500

4000

 

4500

5000

5500

6000

6250

 

 

1 Heater Module

0.02

0.03

0.05

0.07

0.08

 

0.10

0.12

0.14

0.16

0.17

2 Heater Modules

0.03

0.05

0.07

0.09

0.12

 

0.14

0.16

0.19

0.21

0.20

Durablade Economizer

0.02

0.02

0.03

0.04

0.05

 

0.06

0.07

0.08

0.09

0.09

Accessory

 

 

 

 

 

 

 

 

 

 

 

 

EconoMi$er

0.07

0.09

0.13

0.18

0.23

 

0.30

0.36

LEGEND

 

 

 

 

 

 

 

 

 

 

 

FIOP — Factory-Installed Option

*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance tables to deter- mine blower rpm and watts.

FAN RPM AT MOTOR PULLEY SETTINGS* — 548F036-120

UNIT

 

 

 

 

 

MOTOR PULLEY TURNS OPEN

 

 

 

 

 

548F

0

1/2

1

11/2

2

 

21/2

3

31/2

 

4

41/2

5

51/2

6

036†

1000

976

952

928

904

 

880

856

832

 

808

784

760

036**

1455

1423

1392

1360

1328

 

1297

1265

1233

 

1202

1170

1138

1107

1075

048†

1185

1150

1115

1080

1045

 

1010

975

940

 

905

870

835

048**

1455

1423

1392

1360

1328

 

1297

1265

1233

 

1202

1170

1138

1107

1075

060†

1300

1260

1220

1180

1140

 

1100

1060

1020

 

980

940

900

060**

1685

1589

1557

1525

1493

 

1460

1428

1396

 

1364

1332

1300

072††

1460

1420

1380

1345

1305

 

1265

1225

1185

 

1150

1110

1070

072**

1685

1589

1557

1525

1493

 

1460

1428

1396

 

1364

1332

1300

090††

840

815

790

765

740

 

715

690

665

 

635

615

590

090***

935

910

885

860

835

 

810

785

760

 

735

710

685

090**

1080

1025

1007

988

970

 

952

933

915

 

897

878

860

102††

935

910

885

860

835

 

810

785

760

 

735

710

685

102**

1080

1025

1007

988

970

 

952

933

915

 

897

878

860

120††

935

910

885

860

835

 

810

785

760

 

735

710

685

120†

1085

1060

1035

1010

985

 

960

935

910

 

885

860

835

120**

1130

1112

1087

1062

1037

 

1012

987

962

 

937

912

887

862

830

*Approximate fan rpm shown.

†Indicates alternate motor and drive package. **Indicates high-static motor and drive package. ††Indicates standard motor and drive package.

***Indicates alternate drive package only.

52

Page 52
Image 52
Bryant 542J ACCESSORY/FIOP Static PRESSURE* in. wg 548F036-072, ACCESSORY/FIOP Static PRESSURE* in. wg 548F090-120

549B, 548F, 542J specifications

Bryant 542J is a high-efficiency gas furnace that stands out for its reliability and advanced heating technologies. Designed to deliver consistent warmth and comfort in residential settings, it combines innovative engineering with energy-efficient features.

One of the key characteristics of the Bryant 542J is its two-stage heating capability. This means that the furnace can adjust its heat output according to the heating demands of your home. During milder weather, it operates at a lower stage, consuming less energy while still maintaining a comfortable environment. When the temperatures drop, the furnace shifts to its higher capacity, providing the necessary warmth efficiently. This not only enhances comfort but also contributes to lower energy bills.

In addition to its two-stage operation, the Bryant 542J also incorporates a variable-speed blower motor. This technology allows the furnace to adjust the airflow depending on the heating requirements, ensuring an even distribution of warm air throughout the home. The variable-speed blower also operates more quietly than conventional fixed-speed motors, creating a serene indoor environment.

Energy efficiency is a hallmark of the Bryant 542J, boasting an Annual Fuel Utilization Efficiency (AFUE) rating of up to 96.5%. This impressive rating means that a significant portion of the energy consumed is effectively converted into usable heat, resulting in substantial savings on heating costs over time. Furthermore, the furnace is equipped with a sealed combustion system that draws air from outside the home, minimizing energy waste and improving indoor air quality.

Diagnostic features are another highlight of the Bryant 542J, which come equipped with SmartEvap technology. This allows the unit to self-diagnose potential issues, providing homeowners with peace of mind and simplifying maintenance procedures.

Durability is also a key feature of the Bryant 542J. It is constructed with high-quality materials designed to withstand harsh winter conditions, ensuring a long lifespan and reliable performance. Its compact design also allows for flexible installation, making it suitable for various residential layouts.

In summary, the Bryant 542J is more than just a gas furnace; it is a sophisticated heating solution that combines efficiency, comfort, and reliability. With features such as two-stage heating, a variable-speed blower, high AFUE ratings, and advanced diagnostics, it is an excellent choice for homeowners seeking an efficient and effective heating system.