Bryant 542J, 548F manual 549B090,120, PHYSICAL DATA cont

Models: 549B 548F 542J

1 122
Download 122 pages 32.45 Kb
Page 69
Image 69

PHYSICAL DATA (cont)

549B090,120

BASE UNIT 549B

090

 

 

120

 

 

 

NOMINAL CAPACITY (tons)

71/2

 

 

10

 

 

 

OPERATING WEIGHT (lb)

 

 

 

 

 

 

 

Unit

870

 

 

1000

 

 

 

Durablade Economizer

44

 

 

44

 

 

 

EconoMi$er

62

 

 

62

 

 

 

Roof Curb

223

 

 

223

 

 

 

COMPRESSOR

 

Scroll

 

 

 

Quantity

2

 

 

2

 

 

 

Oil (oz) (each compr)

57

 

 

57

 

 

 

REFRIGERANT TYPE

 

R-22

 

 

 

Operating Charge (lb)

 

 

 

 

 

 

 

Circuit 1

9.1

 

 

10.6

 

 

 

 

 

 

 

Circuit 2

9.6

 

 

9.9

 

 

 

OUTDOOR FAN

 

Propeller

 

 

 

Quantity...Diameter (in.)

2...22

 

 

2...22

 

 

 

Nominal Cfm

6500

 

 

6500

 

 

 

Motor Hp...Rpm

1/4...1100

 

 

1/4...1100

 

 

 

OUTDOOR COIL

Enhanced Copper Tubes, Aluminum Fins, Fixed Orifice Metering Device

 

549B036

 

Rows...Fins/in.

2...17

 

 

2...17

 

 

Total Face Area (sq ft)

20.5

 

 

25.1

 

 

 

INDOOR FAN

 

Centrifugal

 

 

 

Size (in.)

15 x 15

 

 

15 x 15

 

 

 

Type Drive

Belt

 

 

Belt

 

-120

 

Nominal Cfm

3000

 

 

4000

 

 

Maximum Continuous Bhp

2.90

 

 

4.20

 

 

 

Motor Frame

56

 

 

56

 

 

 

Fan Rpm Range

725-925

 

 

860-1080

 

 

 

Motor Bearing Type

Ball

 

 

Ball

 

 

 

Maximum Fan Rpm

1725

 

 

2100

 

 

 

Motor Pulley Pitch Diameter

 

 

 

 

 

 

 

A/B (in.)

3.4/4.4

 

 

4.0/5.0

 

 

 

Fan Pulley Pitch Diameter (in.)

8.0

 

 

8.0

 

 

 

Belt — Type...Length (in.)

A...51

 

 

A...51

 

 

 

Pulley Center Line Distance (in.)

16.75-19.25

 

 

15.85-17.50

 

 

 

Fan Shaft Diameter at Pulley (in.)

1

 

 

1

 

 

 

Speed Change per Full Turn of

 

 

 

 

 

 

 

Movable Pulley Flange (rpm)

50

 

 

45

 

 

 

Movable Pulley Maximum Full

 

 

 

 

 

 

 

Turns from Closed Position

5

 

 

5

 

 

 

Factory Setting — Full Turns Open

5

 

 

5

 

 

 

Factory Speed Setting (rpm)

725

 

 

860

 

 

 

INDOOR COIL

Enhanced Copper Tubes, Aluminum Double Wavy Fins, Fixed Orifice Metering Device

 

 

 

Rows...Fins/in.

3...15

 

 

4...15

 

 

 

Total Face Area (sq ft)

8.89

 

 

11.11

 

 

 

HIGH-PRESSURE SWITCH (psig)

 

 

 

 

 

 

 

Standard Compressor Internal Relief

 

625

 

 

 

Cutout

 

428

 

 

 

Reset (Auto.)

 

320

 

 

 

LOSS-OF-CHARGE/LOW-PRESSURE SWITCH

 

 

 

 

 

 

 

(Liquid Line) (psig)

 

 

 

 

 

 

 

Cutout

 

7 ± 3

 

 

 

Reset (Auto.)

 

22 ± 5

 

 

 

FREEZE PROTECTION THERMOSTAT

 

 

 

 

 

 

 

Opens (F)

 

30

 

 

 

Closes (F)

 

45

 

 

 

OUTDOOR-AIR INLET FILTER

 

Cleanable

 

 

 

Quantity...Size (in.)

 

1...20 x 25 x 1

 

 

 

 

1...16 x 25 x 1

 

 

 

 

 

 

 

 

RETURN-AIR FILTERS

 

Throwaway

 

 

 

Quantity...Size (in.)

4...16 x 20 x 2

 

 

4...20 x 20 x 2

 

 

 

LEGEND

Bhp — Brake Horsepower

69

Page 69
Image 69
Bryant 542J, 548F manual 549B090,120, PHYSICAL DATA cont