Bryant 549B, 542J PHYSICAL DATA cont, 548F090-120, 548F036-120, Hermetic, R-22, Propeller Type

Models: 549B 548F 542J

1 122
Download 122 pages 32.45 Kb
Page 20
Image 20
PHYSICAL DATA (cont)

548F036-120

PHYSICAL DATA (cont)

548F090-120

UNIT SIZE 548F

 

090

102

120

NOMINAL CAPACITY (tons)

 

71/2

81/2

10

OPERATING WEIGHT (lb)

 

 

 

 

Unit

 

940

965

1015

Economizer

 

 

 

 

Durablade

 

44

44

44

EconoMi$er

 

62

62

62

Roof Curb*

 

143

143

143

COMPRESSOR

 

 

Hermetic

 

Quantity

 

2

2

2

Oil (oz)

 

45 ea

54 ea

54 ea

REFRIGERANT TYPE

 

 

R-22

 

Operating Charge (lb-oz)

 

 

 

 

Circuit 1

 

5-14

8- 6

7-14

Circuit 2

 

5-13

8-13

8- 3

OUTDOOR COIL

 

Enhanced Copper Tubes, Aluminum Lanced Fins Fixed Orifice Metering Device

Rows...Fins/in.

 

1...17

2...17

2...17

Total Face Area (sq ft)

 

20.50

18.00

18.30

OUTDOOR FAN

 

 

Propeller Type

 

Nominal Cfm

 

6500

6500

6500

Quantity...Diameter (in.)

 

2...22

2...22

2...22

Motor Hp...Rpm

 

1/4...1100

1/4...1100

1/4...1100

Watts Input (Total)

 

500

500

500

INDOOR COIL

 

Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Fixed Orifice Metering Device

Rows...Fins/in.

 

3...15

3...15

3...15

Total Face Area (sq ft)

 

8.0

8.0

11.1

INDOOR FAN

 

 

Centrifugal Type

 

Quantity...Size (in.)

Std

1...15 x 15

1...15 x 15

1...15 x 15

 

Alt

1...15 x 15

1...15 x 15

 

High-Static

1...15 x 15

1...15 x 15

1...15 x 15

Type Drive

Std

Belt

Belt

Belt

 

Alt

Belt

Belt

Nominal Cfm

High-Static

Belt

Belt

Belt

 

3000

3600

4000

Maximum Continuous Bhp

Std

2.40

2.40

2.40

 

Alt

2.40

2.90

 

High-Static

3.70

3.70

5.25

Motor Frame Size

Std

56

56

56

 

Alt

56

56

 

High-Static

56

56

56

Nominal Rpm High/Low

Std

 

Alt

 

High-Static

1725

1725

1725

Fan Rpm Range

Std

590- 840

685- 935

685- 935

 

Alt

685- 935

835-1085

Motor Bearing Type

High-Static

860-1080

860-1080

830-1130

 

Ball

Ball

Ball

Maximum Allowable Rpm

 

2100

2100

2100

Motor Pulley Pitch Diameter Min/Max (in.)

Std

2.4/3.4

2.8/3.8

2.8/3.8

 

Alt

2.8/3.8

3.4/4.4

 

High-Static

4.0/5.0

4.0/5.0

2.8/3.8

Nominal Motor Shaft Diameter (in.)

Std

5/8

5/8

5/8

 

Alt

5/8

7/8

Fan Pulley Pitch Diameter (in.)

High-Static

7/8

7/8

7/8

Std

7.0

7.0

7.0

 

Alt

7.0

7.0

 

High-Static

8.0

8.0

5.8

Belt, Quantity...Type...Length (in.)

Std

1...A...49

1...A...49

1...A...49

 

Alt

1...A...49

1...A...49

 

High-Static

1...A...55

1...A...55

1...BX...46

Pulley Center Line Distance (in.)

Std

16.75-19.25

16.75-19.25

15.85-17.50

 

Alt

15.75-19.25

15.85-17.50

Speed Change per Full Turn of

High-Static

15.75-19.25

16.75-19.25

15.85-17.50

 

 

 

 

Movable Pulley Flange (rpm)

Std

50

50

50

 

Alt

50

50

Movable Pulley Maximum Full Turns

High-Static

60

60

60

 

 

 

 

From Closed Position

Std

5

5

5

 

Alt

5

5

 

High-Static

5

5

6

Factory Setting

Std

5

5

5

 

Alt

5

5

 

High-Static

5

5

5

Factory Speed Setting (rpm)

Std

590

685

685

 

Alt

685

835

Fan Shaft Diameter at Pulley (in.)

High-Static

860

860

887

 

1

1

1

HIGH-PRESSURE SWITCH (psig)

 

 

 

 

Standard Compressor Internal Relief (Differential)

 

 

450 ± 50

 

Cutout

 

 

428

 

Reset (Auto.)

 

 

320

 

LOSS-OF-CHARGE SWITCH (psig)

 

 

 

 

Cutout

 

 

7 ± 3

 

Reset (Auto.)

 

 

22 ± 5

 

FREEZE-PROTECTION THERMOSTAT (F)

 

 

 

 

Opens

 

 

30 ± 5

 

Closes

 

 

45 ± 5

 

OUTDOOR-AIR INLET SCREENS

 

 

Cleanable

 

Quantity...Size (in.)

 

 

1...20 x 25 x 1

 

 

 

 

1...16 x 25 x 1

 

RETURN-AIR FILTERS

 

 

Throwaway

 

Quantity...Size (in.)

 

4...16 x 20 x 2

4...16 x 20 x 2

4...20 x 20 x 2

LEGEND

Bhp — Brake Horsepower *Weight of 14-in. roof curb.

NOTE: The 548F units have a loss-of-charge switch located in the liquid line.

20

Page 20
Image 20
Bryant 549B PHYSICAL DATA cont, 548F090-120, 548F036-120, Hermetic, R-22, Propeller Type, Centrifugal Type, Cleanable