Bryant 542J, 548F manual Performance Data, 549B036-120, Cooling Capacities, 549B036 3 Tons

Models: 549B 548F 542J

1 122
Download 122 pages 32.45 Kb
Page 75
Image 75
549B036 (3 Tons)

PERFORMANCE DATA

COOLING CAPACITIES

549B036 (3 Tons)

 

Temp (F)

 

 

 

Indoor Entering Air — Cfm/Bf

 

 

 

 

Outdoor

 

900/0.13

 

 

 

1200/0.17

 

 

 

1500/0.19

 

Entering Air

 

 

 

Indoor Entering Air — Ewb (F)

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

72

67

62

72

67

62

 

72

67

62

 

 

 

75

TC

41.7

38.4

34.1

43.2

40.3

37.3

 

44.4

41.4

36.8

SHC

20.3

25.0

29.0

21.9

28.0

33.7

 

23.2

30.6

36.8

 

kW

2.22

2.17

2.13

2.23

2.20

2.17

 

2.25

2.21

2.18

85

TC

40.5

37.2

32.4

42.1

39.0

36.0

 

43.1

40.2

37.2

SHC

19.9

24.6

28.1

21.6

27.8

33.2

 

23.1

30.5

36.3

 

kW

2.49

2.45

2.40

2.51

2.48

2.44

 

2.53

2.49

2.45

 

TC

39.1

35.9

30.6

40.8

37.6

33.9

 

42.0

38.7

35.8

Standard Ratings

LEGEND

Bf — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb

kW — Compressor Motor Power Input

SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross

NOTES:

1.Direct interpolation is permissible. Do not extrapolate.

2.The following formulas may be used:

sensible capacity

95

SHC

19.4

24.1

27.2

21.2

27.4

32.2

23.0

30.2

35.8

tldb = tedb

(Btuh)

 

 

kW

2.80

2.75

2.69

2.82

2.78

2.74

 

2.85

2.80

2.76

105

 

TC

37.6

33.9

28.8

39.2

36.0

32.3

 

40.1

37.0

34.6

 

SHC

18.8

23.3

26.3

20.8

26.8

31.4

 

22.3

29.7

34.5

 

 

kW

3.13

3.08

3.01

3.16

3.11

3.06

 

3.18

3.13

3.09

115

 

TC

35.9

31.9

27.9

37.4

34.2

30.2

 

38.3

35.3

32.5

 

SHC

18.2

22.5

25.8

20.2

26.1

30.1

 

21.8

29.0

32.5

 

 

kW

3.49

3.43

3.36

3.52

3.47

3.40

 

3.54

3.50

3.45

125

 

TC

34.2

30.5

26.3

35.5

32.1

28.6

 

36.3

33.2

31.0

 

SHC

17.6

21.9

25.0

19.5

25.3

28.6

 

21.4

28.2

31.0

 

 

kW

3.88

3.81

3.74

3.91

3.85

3.79

 

3.92

3.88

3.84

 

 

 

 

 

 

 

 

 

 

 

 

 

549B048 (4 Tons)

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

Indoor Entering Air — Cfm/Bf

 

 

 

 

Outdoor

 

1200/0.13

 

 

 

1600/0.16

 

 

 

2000/0.19

 

Entering Air

 

 

 

Indoor Entering Air — Ewb (F)

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

72

67

62

 

72

67

62

 

72

67

62

 

 

 

 

 

75

 

TC

53.1

48.7

45.0

 

55.6

49.6

46.7

 

56.1

50.7

48.4

 

SHC

25.1

30.7

36.7

 

27.3

32.6

40.5

 

28.2

35.1

44.6

 

 

kW

2.92

2.86

2.82

 

2.96

2.87

2.84

 

2.96

2.88

2.87

85

 

TC

51.9

47.3

43.7

 

53.9

49.1

45.6

 

54.4

50.2

46.9

 

SHC

24.9

30.2

36.2

 

26.7

33.4

40.4

 

27.7

36.1

44.2

 

 

kW

3.29

3.22

3.19

 

3.32

3.25

3.21

 

3.32

3.27

3.23

95

 

TC

50.5

45.5

42.1

 

51.8

47.4

44.0

 

52.3

47.4

44.6

 

SHC

24.3

29.5

35.6

 

26.0

32.8

39.9

 

27.0

34.3

42.4

 

 

kW

3.70

3.62

3.58

 

3.71

3.65

3.61

 

3.72

3.64

3.61

105

 

TC

48.2

43.7

40.5

 

50.0

45.3

42.2

 

50.8

46.3

43.2

 

SHC

23.6

28.9

35.1

 

25.7

32.0

39.5

 

27.2

34.8

42.4

 

 

kW

4.14

4.06

4.04

 

4.16

4.08

4.05

 

4.18

4.10

4.06

115

 

TC

45.1

42.1

38.2

 

46.4

43.5

39.9

 

46.0

44.4

41.3

 

SHC

22.1

28.7

34.0

 

23.6

31.9

38.6

 

23.8

34.4

41.3

 

 

kW

4.57

4.55

4.50

 

4.59

4.56

4.52

 

4.58

4.57

4.54

125

 

TC

43.2

39.5

36.1

 

43.9

41.2

37.7

 

44.9

41.8

39.6

 

SHC

21.7

27.7

33.0

 

23.0

31.3

37.6

 

24.5

33.9

39.6

 

 

kW

5.10

5.05

5.02

 

5.11

5.08

5.05

 

5.13

5.09

5.08

 

 

 

 

 

 

 

 

 

 

 

 

549B060 (5 Tons)

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

Indoor Entering Air — Cfm/Bf

 

 

 

 

Outdoor

 

1500/0.03

 

 

 

2000/0.05

 

 

 

2500/0.07

 

Entering Air

 

 

 

Indoor Entering Air — Ewb (F)

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

72

67

62

 

72

67

62

 

72

67

62

 

 

 

 

 

75

 

TC

70.4

62.3

52.9

 

73.6

68.2

58.4

 

75.5

69.1

64.9

 

SHC

34.2

42.0

48.1

 

37.8

49.6

57.6

 

41.1

53.8

64.8

 

 

kW

3.75

3.73

3.58

 

3.80

3.80

3.69

 

3.83

3.74

3.75

85

 

TC

68.5

58.9

50.8

 

71.0

65.4

56.5

 

72.7

66.9

62.7

 

SHC

33.6

40.6

47.1

 

37.1

48.5

56.4

 

40.3

53.9

62.6

 

 

kW

4.20

4.16

4.03

 

4.24

4.23

4.12

 

4.27

4.20

4.17

95

 

TC

65.8

55.3

47.4

 

68.8

62.2

53.5

 

70.5

64.0

60.3

 

SHC

32.8

39.2

45.5

 

36.6

47.3

53.5

 

40.2

53.1

60.2

 

 

kW

4.69

4.63

4.49

 

4.75

4.70

4.60

 

4.78

4.68

4.67

105

 

TC

63.0

51.4

43.6

 

65.6

58.1

50.2

 

67.1

60.7

57.5

 

SHC

31.7

37.6

43.6

 

35.6

45.8

50.2

 

39.1

52.1

57.5

 

 

kW

5.22

5.13

5.00

 

5.27

5.21

5.12

 

5.30

5.22

5.20

115

 

TC

59.4

48.2

40.8

 

62.1

52.6

46.8

 

63.7

55.5

52.6

 

SHC

30.6

36.4

40.8

 

34.6

43.7

46.8

 

38.4

50.3

52.5

 

 

kW

5.83

5.70

5.59

 

5.87

5.77

5.70

 

5.89

5.81

5.77

125

 

TC

53.8

44.6

40.4

 

56.8

46.3

43.3

 

59.5

47.8

47.3

 

SHC

28.7

35.0

40.3

 

33.0

41.3

43.3

 

37.3

46.9

47.3

 

 

kW

6.44

6.30

6.21

 

6.50

6.36

6.32

 

6.54

6.40

6.39

1.10 x cfm

tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)

 

 

total capacity

hlwb = hewb

(Btuh)

4.5 x cfm

 

 

Where: hewb = Enthalpy of air entering evaporator coil

3.The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.

Above 80 F edb, add (corr factor x cfm) to SHC.

 

 

 

ENTERING AIR

 

 

 

DRY-BULB TEMP (F)

 

BYPASS

79

78

 

77

76

75

 

under

FACTOR

 

 

75

 

 

 

 

 

 

 

(BF)

81

82

 

83

84

85

 

over

 

 

 

85

 

 

 

 

 

 

 

 

 

 

Correction Factor

 

.05

1.04

2.07

 

3.11

4.14

5.18

 

Use

.10

.98

1.96

 

2.94

3.92

4.90

 

formula

.20

.87

1.74

 

2.62

3.49

4.36

 

shown

.30

.76

1.53

 

2.29

3.05

3.82

 

below.

Interpolation is permissible.

Correction Factor = 1.10 x (1 – BF) x (edb – 80).

549B036-120

75

Page 75
Image 75
Bryant 542J, 548F manual Performance Data, 549B036-120, Cooling Capacities, 549B036 3 Tons