1.10 x cfm

PERFORMANCE DATA (cont)

COOLING CAPACITIES (cont)

548F072 (6 TONS)

Temp (F)

 

 

 

 

 

Indoor Entering Air — Cfm/BF

 

 

 

 

Outdoor

 

1800/0.10

 

 

2400/0.13

 

 

3000/0.19

 

Entering Air

 

 

 

 

 

Indoor Entering Air — Ewb (F)

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

 

67

 

62

72

 

67

 

62

72

 

67

 

62

 

 

 

 

 

 

 

 

 

 

75

 

TC

81.1

 

77.6

 

72.1

84.0

 

80.3

 

75.2

84.2

 

81.1

 

77.8

 

SHC

36.2

 

46.9

 

57.0

39.1

 

52.4

 

65.4

40.8

 

56.2

 

72.2

 

 

kW

5.16

 

5.11

 

5.01

5.23

 

5.16

 

5.06

5.23

 

5.17

 

5.11

85

 

TC

80.7

 

75.8

 

70.0

83.9

 

79.3

 

73.4

84.1

 

80.8

 

76.2

 

SHC

36.1

 

46.5

 

56.4

39.7

 

52.9

 

65.2

41.6

 

58.3

 

71.9

 

 

kW

5.83

 

5.74

 

5.65

5.90

 

5.81

 

5.69

5.90

 

5.84

 

5.76

95

 

TC

79.3

 

73.0

 

67.3

82.0

 

76.7

 

70.8

83.0

 

79.1

 

73.5

 

SHC

35.8

 

45.4

 

55.3

39.3

 

52.3

 

64.3

42.2

 

58.9

 

69.7

 

 

kW

6.54

 

6.37

 

6.28

6.60

 

6.47

 

6.37

6.62

 

6.55

 

6.40

105

 

TC

76.0

 

70.6

 

64.3

79.6

 

73.4

 

67.9

80.7

 

75.5

 

71.3

 

SHC

34.6

 

44.8

 

54.1

38.8

 

51.2

 

62.9

42.0

 

57.6

 

67.8

 

 

kW

7.21

 

7.12

 

6.94

7.34

 

7.15

 

7.06

7.36

 

7.22

 

7.14

115

 

TC

72.7

 

67.5

 

61.1

75.8

 

70.6

 

64.7

77.9

 

71.8

 

68.5

 

SHC

33.6

 

43.7

 

52.7

37.6

 

50.7

 

60.9

41.5

 

56.4

 

65.2

 

 

kW

7.95

 

7.86

 

7.63

8.06

 

7.95

 

7.77

8.14

 

7.94

 

7.90

125

 

TC

70.1

 

63.9

 

57.6

71.8

 

66.9

 

61.6

73.5

 

68.6

 

65.4

 

SHC

32.9

 

42.4

 

51.2

36.4

 

49.5

 

58.4

40.2

 

56.1

 

62.3

 

 

kW

8.82

 

8.62

 

8.37

8.83

 

8.73

 

8.54

8.89

 

8.79

 

8.69

548F090 (71/2 TONS)

Temp (F)

 

 

 

 

 

Indoor Entering Air — Cfm/BF

 

 

 

 

 

Outdoor

2250/0.04

3000/0.06

 

 

3200/0.08

3750/0.11

Entering Air

 

 

 

 

 

Indoor Entering Air — Ewb (F)

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

67

 

62

72

67

 

62

 

72

67

62

72

67

62

 

 

 

 

 

 

75

TC

109.8

101.4

 

92.2

116.2

107.0

 

98.0

 

117.6

108.8

100.2

118.8

110.4

102.4

SHC

44.2

57.4

 

69.4

49.6

66.0

 

82.0

 

51.8

69.8

87.0

54.0

74.0

92.0

 

kW

6.66

6.44

 

6.18

6.86

6.60

 

6.36

 

6.92

6.66

6.42

6.94

6.70

6.48

85

TC

105.2

96.4

 

87.0

111.4

102.2

 

92.6

 

113.0

104.0

95.0

114.6

105.8

97.6

SHC

42.8

55.6

 

67.6

48.4

65.0

 

80.0

 

50.8

69.0

84.4

53.4

73.8

88.8

 

kW

7.20

6.94

 

6.64

7.42

7.14

 

6.82

 

7.48

7.20

6.90

7.54

7.28

7.00

95

TC

100.6

91.0

 

82.0

105.6

96.2

 

87.4

 

107.2

98.0

89.8

108.6

99.6

92.8

SHC

41.6

54.0

 

65.8

47.0

63.2

 

77.8

 

49.4

67.4

81.4

52.0

72.2

84.6

 

kW

7.78

7.42

 

7.08

7.96

7.62

 

7.30

 

8.00

7.70

7.40

8.06

7.76

7.50

105

TC

94.8

85.4

 

76.8

99.8

90.2

 

82.2

 

101.4

91.6

85.0

103.2

93.2

88.0

SHC

40.0

52.2

 

63.8

45.6

61.6

 

74.6

 

48.2

65.8

77.6

51.2

70.4

80.4

 

kW

8.26

7.88

 

7.50

8.48

8.10

 

7.76

 

8.56

8.18

7.88

8.64

8.24

8.02

115

TC

88.8

79.9

 

71.4

93.4

84.0

 

77.6

 

94.8

85.4

80.0

96.0

86.6

83.0

SHC

38.4

50.4

 

61.6

44.2

59.8

 

70.6

 

46.6

64.0

73.2

49.4

68.6

75.8

 

kW

8.76

8.32

 

7.90

8.98

8.54

 

8.22

 

9.04

8.62

8.36

9.10

8.70

8.50

125

TC

82.6

73.8

 

65.8

86.6

77.4

 

74.4

 

88.0

78.8

75.0

89.2

80.0

77.6

SHC

36.8

48.6

 

59.2

42.2

57.8

 

66.2

 

45.2

62.0

68.6

48.2

66.6

71.0

 

kW

9.20

8.74

 

8.30

9.44

8.96

 

8.68

 

9.52

9.02

8.82

9.60

9.12

8.98

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

548F102 (81/2 TONS)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

 

Indoor Entering Air — Cfm/BF

 

 

 

 

 

Outdoor

2400/0.06

 

3200/0.09

 

 

3600/0.11

 

4000/0.14

Entering Air

 

 

 

 

 

 

Indoor Entering Air — Ewb (F)

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

67

 

62

 

72

 

67

 

62

 

 

72

 

67

 

62

 

72

 

67

62

 

 

 

 

 

 

 

 

 

 

 

 

 

75

TC

111.4

102.3

 

91.0

 

115.7

 

108.2

 

97.6

 

 

117.0

 

110.1

 

100.4

 

118.1

 

111.6

102.5

SHC

51.8

64.3

 

75.3

 

54.9

 

71.9

 

87.6

 

 

55.8

 

74.9

 

92.5

 

56.7

 

77.1

96.4

 

kW

8.64

8.48

 

8.23

 

9.32

 

9.18

 

8.95

 

 

9.73

 

9.61

 

9.30

 

10.19

 

10.12

9.72

85

TC

108.8

97.4

 

86.1

 

113.7

 

104.2

 

92.9

 

 

115.2

 

106.6

 

94.8

 

116.6

 

108.3

98.0

SHC

50.9

62.3

 

73.2

 

54.7

 

70.9

 

85.1

 

 

55.7

 

74.3

 

89.3

 

56.7

 

77.2

92.2

 

kW

9.27

9.09

 

8.76

 

9.98

 

9.79

 

9.40

 

 

10.40

 

10.24

 

9.83

 

10.88

 

10.74

10.20

95

TC

104.5

92.7

 

81.2

 

110.4

 

98.8

 

87.7

 

 

112.0

 

101.3

 

90.8

 

113.2

 

103.1

93.8

SHC

49.3

60.2

 

70.9

 

53.7

 

68.7

 

82.4

 

 

55.1

 

72.6

 

86.3

 

56.2

 

75.7

88.2

 

kW

9.90

9.56

 

9.22

 

10.64

 

10.39

 

9.88

 

 

11.07

 

10.86

 

10.25

 

11.55

 

11.36

10.67

105

TC

98.8

87.8

 

75.9

 

105.5

 

93.4

 

83.0

 

 

107.4

 

95.4

 

86.5

 

108.9

 

97.1

89.5

SHC

47.1

58.3

 

68.1

 

52.2

 

66.5

 

79.0

 

 

53.7

 

69.9

 

82.2

 

55.1

 

72.9

83.9

 

kW

10.37

10.08

 

9.70

 

11.26

 

10.90

 

10.33

 

11.71

 

11.34

 

10.73

 

12.20

 

11.82

11.24

115

TC

93.8

82.4

 

71.1

 

98.7

 

87.9

 

78.6

 

 

100.8

 

89.8

 

82.1

 

102.9

 

91.3

85.3

SHC

45.3

56.0

 

65.9

 

49.5

 

64.5

 

75.5

 

 

51.3

 

68.0

 

77.9

 

53.0

 

71.0

79.6

 

kW

10.99

10.56

 

10.13

 

11.72

 

11.39

 

10.79

 

12.16

 

11.86

 

11.24

 

12.76

 

12.38

11.76

125

TC

88.4

77.2

 

66.7

 

93.1

 

82.2

 

74.5

 

 

94.9

 

83.9

 

77.9

 

96.2

 

85.3

80.8

SHC

43.4

54.1

 

63.1

 

47.7

 

62.3

 

71.4

 

 

49.2

 

65.8

 

73.7

 

50.4

 

68.8

75.2

 

kW

11.52

11.03

 

10.56

 

12.33

 

11.87

 

11.30

 

12.78

 

12.33

 

11.75

 

13.29

 

12.81

12.27

LEGEND

BF — Bypass Factor

Edb — Entering Dry-Bulb

Ewb — Entering Wet-Bulb

kW — Compressor Motor Power Input

Ldb — Leaving Dry-Bulb

Lwb — Leaving Wet-Bulb

SHC — Sensible Heat Capacity

(1000 Btuh) Gross

TC — Total Capacity (1000 Btuh) Gross

NOTES:

1.Direct interpolation is permissible. Do not extrapolate.

2.The following formulas may be used:

tldb = tedb sensible capacity (Btuh)

tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving indoor coil (hlwb)

total capacity (Btuh)

hlwb = hewb

4.5 x cfm

Where: hewb = Enthalpy of air entering evap- orator coil

3.The SHC is based on 80 F edb temperature of air entering indoor coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.

Above 80 F edb, add (corr factor x cfm) to SHC.

 

 

ENTERING AIR

 

 

 

DRY-BULB TEMP (F)

BYPASS

79

78

77

76

75

 

under

FACTOR

 

 

 

 

 

 

75

(BF)

81

82

83

84

85

 

over

 

 

85

 

 

 

 

 

 

 

 

 

Correction Factor

 

.05

1.04

2.07

3.11

4.14

5.18

 

Use

.10

.98

1.96

2.94

3.92

4.90

 

formula

.20

.87

1.74

2.62

3.49

4.36

 

shown

.30

.76

1.53

2.29

3.05

3.82

 

below.

Interpolation is permissible.

Correction Factor = 1.10 x (1 – BF) x (edb – 80).

548F036-120

27

Page 27
Image 27
Bryant 542J, 548F, 549B manual Performance Data, Cooling Capacities, Entering AIR DRY-BULB Temp F Bypass

549B, 548F, 542J specifications

Bryant 542J is a high-efficiency gas furnace that stands out for its reliability and advanced heating technologies. Designed to deliver consistent warmth and comfort in residential settings, it combines innovative engineering with energy-efficient features.

One of the key characteristics of the Bryant 542J is its two-stage heating capability. This means that the furnace can adjust its heat output according to the heating demands of your home. During milder weather, it operates at a lower stage, consuming less energy while still maintaining a comfortable environment. When the temperatures drop, the furnace shifts to its higher capacity, providing the necessary warmth efficiently. This not only enhances comfort but also contributes to lower energy bills.

In addition to its two-stage operation, the Bryant 542J also incorporates a variable-speed blower motor. This technology allows the furnace to adjust the airflow depending on the heating requirements, ensuring an even distribution of warm air throughout the home. The variable-speed blower also operates more quietly than conventional fixed-speed motors, creating a serene indoor environment.

Energy efficiency is a hallmark of the Bryant 542J, boasting an Annual Fuel Utilization Efficiency (AFUE) rating of up to 96.5%. This impressive rating means that a significant portion of the energy consumed is effectively converted into usable heat, resulting in substantial savings on heating costs over time. Furthermore, the furnace is equipped with a sealed combustion system that draws air from outside the home, minimizing energy waste and improving indoor air quality.

Diagnostic features are another highlight of the Bryant 542J, which come equipped with SmartEvap technology. This allows the unit to self-diagnose potential issues, providing homeowners with peace of mind and simplifying maintenance procedures.

Durability is also a key feature of the Bryant 542J. It is constructed with high-quality materials designed to withstand harsh winter conditions, ensuring a long lifespan and reliable performance. Its compact design also allows for flexible installation, making it suitable for various residential layouts.

In summary, the Bryant 542J is more than just a gas furnace; it is a sophisticated heating solution that combines efficiency, comfort, and reliability. With features such as two-stage heating, a variable-speed blower, high AFUE ratings, and advanced diagnostics, it is an excellent choice for homeowners seeking an efficient and effective heating system.