Bryant 542J INDOOR-FANMOTOR DATA — 549B036-120, PERFORMANCE DATA cont, Optional Power Exhaust

Models: 549B 548F 542J

1 122
Download 122 pages 32.45 Kb
Page 89
Image 89
INDOOR-FAN MOTOR DATA — 549B036-120

PERFORMANCE DATA (cont)

OPTIONAL POWER EXHAUST

POWER REQUIREMENTS

UNIT

AMPS @ 230 V

MOCP

SIZE

(2 Fans Running)

230 VAC

460 VAC

549B036-072

1.40 Amps @ 60 Hz

15.0 amps

15.0 amps

549B090,120

3.04 Amps @ 60 Hz

 

 

MOCP — Maximum Overcurrent Protection

 

0.25

 

 

 

 

wg)

0.20

 

 

 

 

(in.

 

 

 

 

 

 

 

 

 

PRESSURE

0.15

 

 

 

 

0.10

 

 

 

 

 

 

 

 

 

STATIC

0.05

 

 

 

 

 

 

 

 

 

 

0.00

 

 

 

 

 

0

500

1000

1500

2000

 

549B036-072

 

FLOW (CFM)

 

 

 

549B090,120

 

 

 

 

 

 

 

 

EconoMi$er Barometric Relief

Damper Characteristics

 

2500

 

 

 

 

 

(cfm)

2000

 

 

 

 

 

1500

 

 

 

 

 

FLOW

1000

 

 

 

 

 

500

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

0

0.1

0.2

0.3

0.4

0.5

Manual background 2 FANS OPERATING

Manual background 1 FAN OPERATING

 

5000

 

 

 

 

 

(cfm)

4000

 

 

 

 

2 FANS

3000

 

 

 

 

OPERATING

 

 

 

 

 

FLOW

 

 

 

 

 

2000

 

 

 

 

1 FAN

1000

 

 

 

 

OPERATING

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

0

0.1

0.2

0.3

0.4

0.5

STATIC PRESSURE (in. wg)

STATIC PRESSURE (in. wg)

549B036-120

EconoMi$er Power Exhaust Performance

EconoMi$er Power Exhaust Performance

(549B036-072)

(549B090,120)

INDOOR-FAN MOTOR DATA — 549B036-120

UNIT

UNIT

MAXIMUM

MAXIMUM

UNIT VOLTAGE

MAXIMUM

MOTOR

549B

PHASE

CONTINUOUS BHP*

OPERATING WATTS*

AMP DRAW

EFFICIENCY (%)

 

 

Single

1.20

1000

208/230

5.1

 

036

Three

1.20

1000

208/230

5.1

75

 

460

2.3

 

 

 

 

 

 

 

Single

1.20

1000

208/230

5.1

 

048

Three

1.20

1000

208/230

5.1

75

 

460

2.3

 

 

 

 

 

 

 

Single

1.80

1921

208/230

9.2

 

060

Three

1.80

1921

208/230

6.1

74

 

460

2.7

 

 

 

 

 

 

072

Three

2.40

2120

208/230

6.1

84

460

2.7

 

 

 

 

 

090

Three

2.90

2615

208/230

7.9

80

460

3.6

 

 

 

 

 

120

Three

4.20

3775

208/230

11.1

85

460

5.0

 

 

 

 

 

LEGEND

Bhp — Brake Horsepower Input to Fan

*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using your fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

89

Page 89
Image 89
Bryant INDOOR-FANMOTOR DATA — 549B036-120, PERFORMANCE DATA cont, Optional Power Exhaust, EconoMi$er Barometric Relief