Bryant 542J Electric Heating Capacities, Multiplication Factors, PERFORMANCE DATA cont, 548F036

Models: 549B 548F 542J

1 122
Download 122 pages 32.45 Kb
Page 54
Image 54
ELECTRIC HEATING CAPACITIES

120

PERFORMANCE DATA (cont)

ELECTRIC HEATING CAPACITIES

548F036-

 

 

 

ACCESSORY

ACCESSORY

 

 

 

SINGLE

UNIT

VOLTAGE

ACCESSORY

HEATER

POINT BOX

548F

(60 Hz)

kW

PART NUMBER

PART NO.

 

 

 

CRHEATER---A00

 

 

 

CRSINGLE---A00

 

 

4.4

101

 

208/230

6.5

102

 

8.7

103

 

(single phase)

 

10.5

104

 

 

 

 

13.0*

102*

004

 

 

4.4

101

036

208/230

6.5

102

8.7

103

 

(3 phase)

 

10.5

104

 

 

 

 

16.0

105

 

460

6.0

106

 

8.8

107

 

(3 phase)

11.5

108

 

 

14.0

109

 

 

4.4

101

 

208/230

8.7

103

 

13.0*

102*

004

 

(single phase)

 

17.4*

103*

004

 

 

 

 

21.0*

104*

004

048

208/230

6.5

102

8.7

103

 

(3 phase)

16.0

105

 

 

21.0*

104*

002

 

460

6.0

106

 

11.5

108

 

(3 phase)

14.0

109

 

 

23.0*

108*

 

 

6.5

102

 

208/230

8.7

103

 

13.0*

102*

004

 

(single phase)

 

17.4*

103*

004

 

 

 

 

21.0*

104*

004

 

 

6.5

102

060

208/230

10.5

104

16.0

105

(3 phase)

 

21.0*

104*

002

 

 

 

 

26.5*

105,104

002

 

 

6.0

106

 

460

11.5

108

 

14.0

109

 

(3 phase)

 

23.0*

108*

 

 

 

 

25.5*

109,108

 

 

 

ACCESSORY

ACCESSORY

 

 

 

SINGLE

UNIT

VOLTAGE

ACCESSORY

HEATER

POINT BOX

548F

(60 Hz)

kW

PART NUMBER

PART NO.

 

 

 

CRHEATER---A00

 

 

 

CRSINGLE---A00

 

 

 

 

 

 

6.5

102

 

208/230

10.5

104

 

16.0

105

 

(3 phase)

 

21.0*

104*

002

 

 

072

 

26.5*

105,104

002

 

6.0

106

 

 

 

460

11.5

108

 

14.0

109

 

(3 phase)

 

23.0*

108*

 

 

 

 

25.5*

109,108

 

 

10.4

117

006

 

208/230

16.0

110

006

 

24.8

111

007

 

(3 phase)

 

32.0

112

007

 

 

090,102

 

42.4*

112,117

009

 

13.9

116

006

 

 

 

460

16.5

113

006

 

27.8

114

006

 

(3 phase)

 

33.0

115

006

 

 

 

 

41.7*

114,116

008

 

 

10.4

117

012

 

208/230

16.0

110

012

 

32.0

112

012

 

(3 phase)

 

42.4*

112,117

015

 

 

120

 

50.0*

112,110

015

 

16.5

113

011

 

 

 

460

27.8

114

011

 

33.0

115

011†

 

(3 phase)

 

41.7*

114,116

014

 

 

 

 

50.0*

115,113

014

*Two heater packages required to provide kW indicated.

†On units with factory-installed outlet, use CRSINGLE014A00.

NOTES: The kW ratings shown above are at 240 and 480 v. Use the Multiplication Factors table to determine heater capacity for your particular voltage.

 

MULTIPLICATION FACTORS

 

 

 

 

 

HEATER RATING

VOLTAGE

 

MULTIPLICATION

DISTRIBUTION

 

VOLTAGE

 

FACTOR

V-3-60

 

 

 

 

 

200

 

0.69

240

208

 

0.75

230

 

0.92

 

 

 

240

 

1.00

480

440

 

0.84

460

 

0.92

 

480

 

1.00

575

545

 

0.90

575

 

1.00

 

600

 

1.09

EXAMPLE: 32.0 kW (at 240 v) heater on 208 v

=32.0 (.75 mult factor)

=24.0 kW capacity at 208 v.